{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24110","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24110","canonicalUrl":"https://aoctrl.com/schneider/ENW24110","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24110","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW24110, 3P circuit breaker, 1000 A at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, fixed mount.","salesMarkdown":"Its 50 kA Icu at 220…440 V AC (42 kA at 690 V) means it can safely interrupt fault currents up to that level without upstream cascading — critical for selectivity studies in low-voltage switchgear. It carries IEC 60947-2 certification, which covers the breaking capacity, utilization category B, and the 12 kV impulse withstand voltage (Uimp) that governs clearance and creepage in the panel. The IP40 enclosure keeps tools and fingers out but does not seal against water; mount it in a cabinet if washdown is nearby. ## Integration — what fits and what does not Fixed mounting on a base plate, rear connections with a 115 mm pitch without spreader. The 422 mm width, 352 mm height, and 297 mm depth mean it occupies a full compartment in a typical low-voltage switchboard — plan for a dedicated cubicle. Vertical or horizontal connection orientation is supported, but the rear-entry terminals dictate bus-bar routing behind the panel. ## Key electrical ratings at a glance Rated operational voltage (Ue) is 690 V AC; rated insulation voltage (Ui) is 1000 V AC. Short-time withstand (Icw) is 50 kA for 1 s at 440 V, 42 kA for 1 s at 690 V, and 25 kA for 3 s at 440/690 V, which supports selective coordination with downstream devices. Maximum breaking time is 25 ms; maximum closing response time is 70 ms.","metaTitle":"Schneider Electric ENW24110 EasyPact NW Circuit Breaker, 100","metaDescription":"Schneider Electric ENW24110 EasyPact NW circuit breaker, 1000 A rated current, 50 kA breaking capacity at 440 V, IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"422 mm","title":"ENW24110","Height":"352 mm","Standards":"IEC 60947-2","description":"Circuit breaker frame, adapt EasyPact NW, 3 Poles, 1000A, N, fixed","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW10N","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"1000 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"N","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"1000 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5a619a9f9d2d87bbc95694fd4b3e6014.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW24110/circuit-breaker-frame-adapt-easypact-nw-3-poles-1000a-n-fixed/"},"ai":{"faq":[{"question":"Where can I buy the ENW24110 and how is it quoted?","answer":"The ENW24110 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote."},{"question":"What is the breaking capacity of the ENW24110?","answer":"The ENW24110 has a breaking capacity (Icu) of 50 kA at 220…440 V AC and 42 kA at 690 V AC, both per IEC 60947-2."},{"question":"What standards does the ENW24110 comply with?","answer":"The ENW24110 is certified to IEC 60947-2 for circuit breakers, including pollution degree 4 per IEC 60664-1."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24110","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24110 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}