{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24112","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24112","canonicalUrl":"https://aoctrl.com/schneider/ENW24112","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24112","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW24112, 3-pole circuit breaker, 1600 A at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2.","salesMarkdown":"The ENW24112 is a 3-pole air circuit breaker from the Schneider Electric EasyPact NW range, rated 1600 A at 40 °C. At 690 V AC the Icu drops to 42 kA, still substantial for most industrial supplies. The Ics (service breaking capacity) matches the Icu at each voltage level — 50 kA and 42 kA respectively — so after clearing a fault at full rating the breaker remains fit for further service, not just a one-shot device. ## Deployment context Fixed-mount design on a base plate, with rear connections and a vertical or horizontal orientation. The 422 mm width, 352 mm height, and 297 mm depth define the panel cutout and enclosure size — plan for a dedicated compartment in the switchboard, not a DIN-rail clip-in. IP40 protection means it's suitable for indoor panel installation where no water spray is present. The push-button control type provides local manual operation for maintenance switching and isolation.","metaTitle":"Schneider Electric ENW24112 EasyPact NW Circuit Breaker, 160","metaDescription":"Schneider Electric ENW24112 EasyPact NW circuit breaker, 1600 A rated current, 50 kA breaking capacity at 440 V, IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"422 mm","Height":"352 mm","Standards":"IEC 60947-2","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW16N","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"1600 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"N","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"1600 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/01c15a61f462a9ee320c37bbfe647eea.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW24112/circuit-breaker-frame-adapt-easypact-nw-3-poles-1600a-n-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24112/alternatives.json"},"ai":{"faq":[{"question":"What is ENW24112's breaking capacity?","answer":"The breaking capacity is 50 kA Icu at 220...440 V AC and 42 kA Icu at 690 V AC, both per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24112","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24112 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}