{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24113","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24113","canonicalUrl":"https://aoctrl.com/schneider/ENW24113","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24113","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW24113, 3P circuit breaker, 2000 A at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2, fixed mounting, IP40.","salesMarkdown":"It carries a 50 kA Icu breaking capacity at 220...440 V AC and 42 kA at 690 V AC, both per IEC 60947-2. The breaker is Category B (selective) per IEC 60947-2, so it coordinates with downstream devices: a short-time withstand rating of 50 kA for 1 second at 440 V lets it ride through a fault long enough for a branch breaker to clear, keeping the main bus live. The 12 kV impulse withstand voltage (Uimp) confirms it handles surge events common in industrial power systems. Fixed-mount design on a base plate — no draw-out cradle. Rear connections with a 115 mm pitch (without spreader) for vertical or horizontal busbar orientation. Dimensions: 422 mm wide × 352 mm high × 297 mm deep. IP40 protection — tool-accessible openings only; no washdown rating. The push-button control on the front cover gives local open/close/reset without opening the door.","metaTitle":"Schneider Electric ENW24113 EasyPact NW Circuit Breaker, 200","metaDescription":"Schneider Electric ENW24113 EasyPact NW circuit breaker, 2000 A rated current, 50 kA breaking capacity at 440 V AC, IEC 60947-2. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"422 mm","Height":"352 mm","Standards":"IEC 60947-2","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW20N","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"2000 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"N","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"2000 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9bc8a470c6e6a8dbc9475320ee9666b4.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24113/circuit-breaker-frame-adapt-easypact-nw-3-poles-2000a-n-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24113/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the ENW24113 and what is the lead time?","answer":"The ENW24113 is sourced to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm lead-time and price quote."},{"question":"What is the breaking capacity of the ENW24113?","answer":"The ENW24113 has a rated ultimate breaking capacity (Icu) of 50 kA at 220...440 V AC and 42 kA at 690 V AC, both per IEC 60947-2. The service breaking capacity (Ics) is the same 50 kA / 42 kA respectively, meaning the breaker can be reclosed after a fault at those levels without derating."},{"question":"What standards does the ENW24113 comply with?","answer":"The ENW24113 is designed and tested to IEC 60947-2 for low-voltage switchgear and controlgear. It is suitable for isolation per that standard, carries a pollution degree 4 rating per IEC 60664-1, and has a 12 kV impulse withstand voltage (Uimp)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24113","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24113 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}