{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24118","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24118","canonicalUrl":"https://aoctrl.com/schneider/ENW24118","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24118","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, circuit breaker, ENW24118, 1000 A at 40 °C, 50 kA Icu at 440 V AC, 4P, drawout, IP40.","salesMarkdown":"The ENW24118 is a 4-pole EasyPact NW drawout circuit breaker rated 1000 A at 40 °C. That 1000 A continuous rating is the thermal current — sized for the main feeder or a large distribution bus, not a branch circuit. The 50 kA Icu at 220…440 V AC tells you it can safely interrupt a fault up to that level without failing; the 42 kA Icu at 690 V covers higher-voltage installations. IP40 keeps tools and fingers out but expects a panel enclosure for washdown areas. ## Drawout integration and panel fit Drawout mounting means the breaker slides into a cradle — no need to disconnect main cables for maintenance or swap. The rear connection and 115 mm connection pitch without spreader define the bus-bar or cable layout; vertical or horizontal connection positions give flexibility in the switchgear lineup. Rail mounting support and the 556 mm width, 439 mm height, 395 mm depth set the enclosure cutout and compartment size. Neutral position left matters if you're paralleling with an existing bus run. ## Durability and electrical endurance Category B utilisation means the breaker is designed for distribution duty with infrequent switching — not for motor starting. Electrical durability is 6000 cycles at 440 V and 4000 cycles at 690 V without maintenance. Mechanical durability is 20000 cycles with maintenance, 10000 without. Maximum breaking time is 25 ms, and maximum closing response time is 70 ms — fast enough for selective coordination in a tiered distribution system.","metaTitle":"Schneider Electric ENW24118 EasyPact NW Circuit Breaker, 100","metaDescription":"Schneider Electric ENW24118 EasyPact NW drawout circuit breaker, 1000 A rated at 40 °C, 50 kA Icu at 440 V. IEC 60947-2, IP40. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"556 mm","Height":"439 mm","Standards":"IEC 60947-2","Control type":"Push-button","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW10N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","[In] rated current":"1000 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"N","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"1000 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Neutral protection setting":"Without protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)","Protected poles description":"4P 4d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/46285c2c14fadb3c96ccf8d83c68160d.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW24118/circuit-breaker-frame-adapt-easypact-nw-4-poles-1000a-n-withdrawal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24118/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of ENW24118?","answer":"50 kA Icu at 220…440 V AC and 42 kA Icu at 690 V AC, both per IEC 60947-2. The Ics (service breaking capacity) matches those values."},{"question":"Where can I buy ENW24118 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock or price figures on this page."},{"question":"What compliance documentation does Schneider provide for ENW24118?","answer":"The breaker is designed to IEC 60947-2 and carries pollution degree 4 per IEC 60664-1. For specific RoHS, REACH, or UL documentation, request the manufacturer's declaration of compliance with your RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24118","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24118 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}