{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24128","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24128","canonicalUrl":"https://aoctrl.com/schneider/ENW24128","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24128","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, ENW24128, fixed-mount circuit breaker, 1600 A at 40 °C, 50 kA Icu at 440 V AC, 4P, IP40.","salesMarkdown":"The Schneider Electric ENW24128 is a fixed-mount EasyPact NW circuit breaker rated 1600 A at 40 °C, with a breaking capacity of 50 kA Icu at 220...440 V AC 50/60 Hz per IEC 60947-2. It is a 4-pole device (4P 4d) with rear vertical/horizontal connections and a 115 mm connection pitch without spreader. The IP40 enclosure suits indoor distribution panels where dust and accidental contact are the main concerns — not washdown or outdoor exposure. Pollution degree 4 per IEC 60664-1 means the internal clearances are designed for conductive dust or heavy condensation environments — a step above the usual PD3 found in commercial gear. ## Deployment context This breaker mounts fixed to a base plate (not DIN rail) with rear connections — typical for large low-voltage switchboards in industrial or utility distribution. The 537 mm width, 352 mm height, and 297 mm depth require a dedicated compartment; plan for busbar and cable entry clearance on the rear side. The push-button control type means manual open/close on the front face, with a contact position indicator for visual status.","metaTitle":"Schneider Electric ENW24128 EasyPact NW Circuit Breaker, 160","metaDescription":"Schneider Electric ENW24128 EasyPact NW circuit breaker, 1600 A rated at 40 °C, 50 kA Icu at 440 V AC, IEC 60947-2. Current lifecycle stage. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","Height":"352 mm","Standards":"IEC 60947-2","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW16N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","[In] rated current":"1600 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"N","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"1600 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Neutral protection setting":"Without protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)","Protected poles description":"4P 4d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/116c70abacb5d8115c35f29448ab2675.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24128/circuit-breaker-frame-adapt-easypact-nw-4-poles-1600a-n-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24128/alternatives.json"},"ai":{"faq":[{"question":"How do I get current pricing and availability for ENW24128?","answer":"Pricing and availability are confirmed at quote time against an RFQ. Submit a request through the storefront for a current quote on this order code."},{"question":"What is ENW24128's listed depth?","answer":"The depth is 297 mm, with a width of 537 mm and height of 352 mm."},{"question":"What is ENW24128's range?","answer":"It belongs to the EasyPact NW range of low-voltage circuit breakers from Schneider Electric."},{"question":"What compliance documentation does this brand provide for ENW24128?","answer":"The breaker is designed to IEC 60947-2 and carries a pollution degree 4 rating per IEC 60664-1. Specific RoHS/REACH/UL documentation should be requested at quote time — the evidence does not list those certifications directly."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24128","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24128 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}