{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24133","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24133","canonicalUrl":"https://aoctrl.com/schneider/ENW24133","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24133","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, circuit breaker, ENW24133, 3P, 800 A at 40 °C, 66 kA Icu at 440 V AC, drawout, IP40.","salesMarkdown":"The Schneider Electric ENW24133 is an EasyPact NW drawout circuit breaker rated 800 A at 40 °C, with a 66 kA Icu breaking capacity at 220...440 V AC (50/60 Hz) per IEC 60947-2. Three-pole, 3d protected, with a drawout mechanism for racking in and out of the cradle without disturbing the power connections. IP40 enclosure keeps out tools and fingers but not water — install in a dry indoor switchgear lineup. The H breaking capacity code (66 kA Icu at 440 V) puts this in the high-interrupting tier for its frame size. Service breaking capacity Ics is 65 kA at the same voltage — meaning after clearing a 65 kA fault the breaker is still rated to carry and switch load current, not just a one-shot device. Short-time withstand Icw is 65 kA for 1 s at 440 V, which supports downstream selectivity with other breakers in the same lineup. Rated insulation voltage Ui is 1000 V AC, impulse withstand Uimp is 12 kV — the breaker handles the transient surges common in industrial distribution without flashover. Dimensions: 441 mm wide, 439 mm high, 395 mm deep. That depth includes the drawout mechanism and arc chutes — measure the enclosure depth to confirm the breaker racks in fully without door interference.","metaTitle":"Schneider Electric ENW24133 EasyPact NW Circuit Breaker, 800","metaDescription":"Schneider Electric ENW24133 EasyPact NW drawout circuit breaker, 800 A rated at 40 °C, 66 kA Icu at 440 V AC, IEC 60947-2. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"441 mm","Height":"439 mm","Standards":"IEC 60947-2","Control type":"Push-button","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW08H","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"800 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"H","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"800 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/f9097edd7b8b0aef78777b7b275dfc98.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24133/circuit-breaker-frame-adapt-easypact-nw-3-poles-800a-h-withdrawal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24133/alternatives.json"},"ai":{"faq":[{"question":"What is ENW24133's breaking capacity at 440 V?","answer":"The ENW24133 has a 66 kA Icu breaking capacity at 220...440 V AC 50/60 Hz per IEC 60947-2, with a service breaking capacity Ics of 65 kA at the same voltage."},{"question":"What compliance documentation does this brand provide for ENW24133?","answer":"The ENW24133 is designed to IEC 60947-2 and carries suitability for isolation per that standard. It is rated for pollution degree 4 per IEC 60664-1. Specific RoHS, REACH, or UL documentation should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24133","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24133 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}