{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24160","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24160","canonicalUrl":"https://aoctrl.com/schneider/ENW24160","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24160","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, circuit breaker, ENW24160, 1600 A at 40 °C, 66 kA Icu at 440 V AC, 4P, IP40, IEC 60947-2.","salesMarkdown":"The Schneider Electric ENW24160 is a 4-pole EasyPact NW circuit breaker rated for 1600 A at 40 °C, with a breaking capacity of 66 kA Icu at 220–440 V AC and 50 kA Icu at 690 V AC per IEC 60947-2. The 1600 A rated current (In) at 40 °C sets the continuous load it can carry in a typical 40 °C enclosure ambient. If your panel runs hotter, you'll need to derate — the IEC 60947-2 standard governs that curve. At 690 V the Icu drops to 50 kA, so verify your system voltage against that ceiling. The IP40 enclosure keeps out tools and debris larger than 1 mm but is not washdown-rated; mount it inside a panel or enclosure for wet-area duty. Fixed mounting on a base plate, rear connection with a 115 mm pitch without spreader. The 537 mm width, 352 mm height, and 297 mm depth mean it needs a substantial cutout in the panel floor — plan for a dedicated compartment, not a shared DIN-rail section. Neutral position is left; the 4P 4d configuration protects all poles including the neutral. Push-button control with a contact position indicator gives local status without opening the door.","metaTitle":"Schneider Electric ENW24160 EasyPact NW Circuit Breaker, 160","metaDescription":"Schneider Electric ENW24160 EasyPact NW circuit breaker, 1600 A rated current, 66 kA Icu at 440 V, IEC 60947-2. Current lifecycle stage. Available to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","Height":"352 mm","Standards":"IEC 60947-2","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"66 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW16H","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","[In] rated current":"1600 A at 40 °C","Connection position":"Horizontal Vertical","Utilisation category":"Category B","Electrical durability":"Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"H","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"1600 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Neutral protection setting":"Without protection (3D) 0.5 x Ir (3D + N/2) 1 x Ir (4D)","Protected poles description":"4P 4d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4751803d8388f83ae5e01b2388c53690.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW24160/circuit-breaker-frame-adapt-easypact-nw-4-poles-1600a-h-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24160/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy ENW24160 and get current pricing?","answer":"The ENW24160 is sourced and quoted to order against an RFQ through independent distribution; availability and current pricing are confirmed at quote time."},{"question":"What is the breaking capacity of ENW24160 at 440 V?","answer":"The ENW24160 has a breaking capacity of 66 kA Icu at 220–440 V AC and 65 kA Ics at the same voltage per IEC 60947-2."},{"question":"What standards does ENW24160 comply with?","answer":"The ENW24160 complies with IEC 60947-2 for circuit breakers and IEC 60664-1 for pollution degree 4 insulation coordination."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24160","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24160 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}