{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24166","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24166","canonicalUrl":"https://aoctrl.com/schneider/ENW24166","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24166","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW switch disconnector, ENW24166, 1000 A AC-23A at 690 V AC, 3 poles, drawout mounting, IP40.","salesMarkdown":"Its headline rating is 1000 A in utilisation category AC-23A at 690 V AC — that means it can make and break motor loads, including occasional inrush, up to that current without maintenance, per IEC 60947-3. For isolation duty, the same standard certifies it as a disconnector: the contact position indicator (visible gap) confirms the circuit is dead when open. ## Withstand and making capacity — the fault-handling backbone Rated short-time withstand current (Icw) is 50 kA for 1 second, or 25 kA for 3 seconds, at ambient temperatures up to 70 °C. That 50 kA / 1 s figure governs selectivity coordination with upstream protection — the switch must hold closed through the clearing time of a downstream breaker. The rated short-circuit making capacity (Icm) is 105 kA AC, which is the peak current the switch can close onto without welding contacts. Impulse withstand voltage (Uimp) is 12 kV, matching the insulation coordination for a 1000 V rated insulation voltage (Ui) system. ## Mounting and integration — drawout chassis, rear connection Drawout mounting on a rail, with rear horizontal or vertical connection at a 115 mm pitch without spreader. The drawout feature means the switch chassis can be racked out for maintenance or replacement without disturbing the main bus connections — a standard requirement for switchgear where uptime matters. IP40 enclosure protection keeps tools and fingers out but is not rated for washdown. Mechanical durability is 20,000 cycles with maintenance or 10,000 without; electrical durability for AC-23A is 6,000 cycles at 440 V and 4,000 at 690 V.","metaTitle":"Schneider Electric ENW24166 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24166 EasyPact NW switch disconnector, 1000 A AC-23A at 690 V, 3 poles, drawout. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"395 mm","Width":"441 mm","Height":"439 mm","Current":"AC-23 A: 1000 A AC 50/60 Hz 690 V","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","IP Rating":"IP40","Application":"Distribution","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm without spreader","Pollution Degree":"4 conforming to IEC 60664-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-3","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C without control unit","Utilization Category":"AC-23 A","Main Product Or Component Type":"Switch disconnector","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/22539e6a622179e8217b91a4786a08c8.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW24166/switch-disconnector-easypact-nw-1000a-n-3-poles-withdrawal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24166/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24166","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24166 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}