{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24185","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24185","canonicalUrl":"https://aoctrl.com/schneider/ENW24185","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24185","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, switch disconnector, ENW24185, 2000 A, 4 poles, drawout, 690 V AC, IP40.","salesMarkdown":"The Schneider Electric ENW24185 is a 4-pole switch disconnector from the EasyPact NW family, rated for 2000 A continuous duty in AC-23A utilisation at 690 V AC. It's a drawout unit — mounts on a rail, rear-connected, with the neutral on the left. That AC-23A rating means it's built to handle motor loads and other high-inrush switching, not just resistive circuits. The 50 kA short-time withstand for 1 second (105 kA making capacity) tells you it can ride through a fault without welding contacts, which is the kind of margin a distribution panel needs when the upstream breaker isn't sized tight. The 1000 V rated insulation voltage (Ui) and 12 kV impulse withstand (Uimp) confirm this switch is suitable for isolation per IEC 60947-3 — you can lock it out and work downstream with confidence. The IP40 enclosure keeps fingers and tools out but isn't sealed against water, so it belongs inside a cabinet, not out on the floor.","metaTitle":"Schneider Electric ENW24185 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24185 EasyPact NW switch disconnector, 2000 A, 4 poles, drawout. Rated 690 V AC, IEC 60947-3. Active production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"395 mm","Width":"556 mm","Height":"439 mm","Current":"AC-23 A: 2000 A AC 50/60 Hz 690 V","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","IP Rating":"IP40","Application":"Distribution","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm without spreader","Pollution Degree":"4 conforming to IEC 60664-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-3","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C without control unit","Utilization Category":"AC-23 A","Mechanical Life Cycles":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Main Product Or Component Type":"Switch disconnector","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b69ff638d4b3f007b77853016d234937.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24185/switch-disconnector-easypact-nw-2000a-n-4-poles-withdrawal/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24185/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24185","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24185 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}