{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24187","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24187","canonicalUrl":"https://aoctrl.com/schneider/ENW24187","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24187","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW switch disconnector, ENW24187, 3200 A AC-23A, 4 poles, drawout mounting, 690 V AC, IP40.","salesMarkdown":"The Schneider Electric ENW24187 is a 4-pole switch disconnector from the EasyPact NW range, rated for 3200 A in AC-23A duty at 690 V AC. It's certified as a disconnector (isolator) per IEC 60947-3, so it provides visible-break isolation for a feeder or distribution panel. Rated operational current of 3200 A in AC-23A at 690 V. This governs motor feeder applications. Short-time withstand (Icw) is 50 kA for 1 second or 25 kA for 3 seconds — that tells you the switch can ride through a fault until an upstream breaker clears it, without welding shut or exploding. The making capacity of 105 kA peak confirms it can close onto a bolted fault and survive. Rated insulation voltage (Ui) of 1000 V AC and impulse withstand (Uimp) of 12 kV give headroom for 690 V systems and cover surge coordination in industrial networks. IP40 protection means it's splash-proof from tools and fingers but not water jets — install inside a panel or enclosure. ## Mechanical and electrical endurance Electrical durability is 5000 cycles at 440 V and 2500 cycles at 690 V under AC-23A without maintenance — that's the contact wear life. Mechanical durability is 20000 cycles with maintenance, 10000 without. For a drawout switch at this current level, those numbers are typical for a main feeder disconnector that sees infrequent operation.","metaTitle":"Schneider Electric ENW24187 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24187 EasyPact NW switch disconnector, 3200A AC-23A, 4 poles, drawout mount. IEC 60947-3, IP40. Active production. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"556 mm","title":"ENW24187","Height":"439 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 3200A, N, 4 Poles, withdrawal","Control type":"Push-button","Network type":"AC","Mounting mode":"Drawout","Product weight":"120 kg","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW32N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Horizontal Vertical","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 3200 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"105 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/00a862fe3e504406f71e0984d8de78b9.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24187/switch-disconnector-easypact-nw-3200a-n-4-poles-withdrawal/"},"ai":{"faq":[{"question":"What is ENW24187's listed depth?","answer":"The ENW24187 has a depth of 395 mm, with width 556 mm and height 439 mm."},{"question":"What compliance documentation does Schneider provide for ENW24187?","answer":"The ENW24187 is certified to IEC 60947-3 for switch-disconnector function and isolation suitability. Pollution degree 4 per IEC 60664-1. Specific RoHS/REACH/UL declarations should be requested with the RFQ."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24187","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24187 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}