{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24192","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24192","canonicalUrl":"https://aoctrl.com/schneider/ENW24192","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24192","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, switch disconnector, ENW24192, 1600 A AC-23A, 4 poles, fixed mount, IP40.","salesMarkdown":"The Schneider Electric ENW24192 is a 4-pole switch disconnector from the EasyPact NW range, rated 1600 A in AC-23A utilisation category at 690 V AC. The 1600 A continuous rating is the headline number, but the short-time withstand current tells you what it survives in a fault: 50 kA for 1 s or 25 kA for 3 s, both per IEC 60947-3. That's enough to coordinate with most downstream MCCB or fuse protection without the switch becoming the weak link. The making capacity of 105 kA peak means it can close onto a bolted fault — important if you're using it as a load-break switch ahead of a transformer or large drive. Pollution degree 4 is the highest in IEC 60664-1, covering conductive pollution (dust, moisture, carbon) that would track across insulation in a dirty substation or industrial environment. That, plus the 12 kV impulse withstand, tells you this switch is designed for main incoming or distribution positions where the environment is harsh and the fault energy is high.","metaTitle":"Schneider Electric ENW24192 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24192 EasyPact NW switch disconnector, 1600 A AC-23A, 4 poles, fixed mount. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","title":"ENW24192","Height":"352 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 1600A, N, 4 Poles, fixed","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","Product weight":"50 kg","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW16N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Horizontal Vertical","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 1600 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"105 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5ac1ce198ed2f8a3aecb35c912659d6d.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24192/switch-disconnector-easypact-nw-1600a-n-4-poles-fixed/"},"ai":{"faq":[{"question":"What is ENW24192's listed depth (297 mm) on this component line?","answer":"The ENW24192 has a depth of 297 mm. That's the panel depth required behind the mounting plate for the switch body and rear connections."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24192","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24192 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}