{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24193","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24193","canonicalUrl":"https://aoctrl.com/schneider/ENW24193","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24193","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, switch disconnector, ENW24193, 2000 A AC-23A, 690 V AC, 4P, fixed mount, IP40.","salesMarkdown":"## What this switch disconnector delivers The Schneider Electric ENW24193 is a 4-pole switch disconnector from the EasyPact NW family, rated for 2000 A in AC-23A duty at 690 V AC — that means it handles heavy motor loads and mixed resistive-inductive circuits common in distribution panels, not just simple resistive switching. The AC-23A utilisation category covers occasional switching of motors, transformers, and capacitor banks, so this part is sized for feeder or main disconnect roles where high inrush currents are expected. Rated short-time withstand current is 50 kA for 1 s (25 kA for 3 s) per IEC 60947-3, and short-circuit making capacity reaches 105 kA AC — selectivity and fault-closure capability are built in for high-fault-level installations. Fixed mounting on a base plate. Rear connection, vertical or horizontal orientation. Neutral on the left. Connection pitch is 115 mm without spreader. Dimensions: 537 mm wide, 352 mm high, 297 mm deep.","metaTitle":"Schneider Electric ENW24193 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24193 EasyPact NW switch disconnector, 2000 A rated operational current, 690 V AC, 4 poles, IP40, IEC 60947-3. Active production. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","title":"ENW24193","Height":"352 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 2000A, N, 4 Poles, fixed","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW20N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Vertical Horizontal","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 2000 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"105 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1bddbb10e1c93fe612f261397538244d.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24193/switch-disconnector-easypact-nw-2000a-n-4-poles-fixed/"},"ai":{"faq":[{"question":"Where can I buy ENW24193 and what is the lead time?","answer":"This part is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here."},{"question":"What are the key ratings for the ENW24193?","answer":"Rated operational current 2000 A in AC-23A at 690 V AC. Short-time withstand current 50 kA for 1 s. Short-circuit making capacity 105 kA AC. Rated impulse withstand voltage 12 kV. Pollution degree 4. IP40 protection."},{"question":"What compliance documentation does Schneider provide for ENW24193?","answer":"The part is designed and tested to IEC 60947-3 for switch-disconnector performance, including isolation suitability. Specific RoHS, REACH, or UL documentation should be requested at RFQ time — the evidence does not list those certificates directly."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24193","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24193 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}