{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24194","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24194","canonicalUrl":"https://aoctrl.com/schneider/ENW24194","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24194","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, switch disconnector, ENW24194, 2500 A AC-23A, 690 V AC, 4 poles, fixed mounting, IP40.","salesMarkdown":"The Schneider Electric ENW24194 is an EasyPact NW switch disconnector rated for 2500 A in AC-23A duty at 690 V AC, 50/60 Hz, with four poles. The AC-23A utilisation category covers switching of motor loads and other highly inductive loads — the 2500 A rating is the operational current at 690 V for that duty, not a resistive-heater rating. For short-circuit conditions, the switch can make onto 105 kA peak (Icm) and withstand 50 kA for 1 second (Icw), which gives the panel designer headroom for high-fault installations. Pollution degree 4 per IEC 60664-1 means the switch is rated for harsh environments where conductive pollution (dust, moisture) may occur — typical in heavy industrial switchrooms or outdoor enclosures. The IP40 enclosure rating keeps tools and fingers out but is not washdown-rated; install it inside a panel if the ambient is wet.","metaTitle":"Schneider Electric ENW24194 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24194 EasyPact NW switch disconnector, 2500 A rated operational current, 690 V AC, 4 poles, IEC 60947-3. Active production. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","title":"ENW24194","Height":"352 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 2500A, N, 4 Poles, fixed","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW25N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Horizontal Vertical","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 2500 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"105 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/4d2dc3484d87c7b15bc5e324765f8f36.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24194/switch-disconnector-easypact-nw-2500a-n-4-poles-fixed/"},"ai":{"faq":[{"question":"What are the key ratings of ENW24194?","answer":"Rated operational current 2500 A in AC-23A at 690 V AC, 4 poles, rated short-time withstand current 50 kA for 1 s, rated short-circuit making capacity 105 kA peak, rated insulation voltage 1000 V, impulse withstand 12 kV."},{"question":"What standards does ENW24194 comply with?","answer":"It complies with IEC 60947-3 for switch-disconnectors and IEC 60664-1 for insulation coordination (pollution degree 4)."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24194","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24194 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}