{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24216","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24216","canonicalUrl":"https://aoctrl.com/schneider/ENW24216","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24216","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, switch disconnector, ENW16H, 1600 A AC-23A, 4 poles, drawout, 1000 V insulation, 66 kA Icw.","salesMarkdown":"## Switch disconnector for distribution, 1600 A AC-23A The Schneider Electric ENW24216 is a 4-pole switch disconnector from the EasyPact NW series, rated for 1600 A in AC-23A utilization category at 690 V AC. The drawout mounting (withdrawal) lets you rack the unit out for inspection or replacement without disturbing the main bus connections, which matters in switchgear where downtime for panel access is the constraint. Rated insulation voltage is 1000 V AC, with an impulse withstand of 12 kV per IEC 60947-3. The short-time withstand current is 66 kA for 1 s, and the making capacity hits 143 kA peak — numbers that tell you this disconnector lives in a high-fault-capacity distribution board, not a light-duty panel. Drawout chassis mounts on a rail (mounting support: rail), with rear connection points at a 115 mm pitch without spreader. The neutral position is left, and connection orientation accepts both vertical and horizontal bus arrangements. Panel cutout planning: width 556 mm, height 439 mm, depth 395 mm — that depth is the through-panel envelope, so verify the cabinet depth clears the rear connection hardware before committing the gland plate. Mechanical durability is 20,000 cycles with maintenance, 10,000 without; electrical endurance at 440 V AC is 6,000 cycles under AC-23A duty.","metaTitle":"Schneider Electric ENW24216 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24216 EasyPact NW switch disconnector, 1600 A rated operational current in AC-23A, 4 poles, drawout mounting. IEC 60947-3. Active production. Sourced to order","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"556 mm","title":"ENW24216","Height":"439 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 1600A, H, 4 Poles, withdrawal","Control type":"Push-button","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW16H","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Vertical Horizontal","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Breaking capacity code":"HA","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 1600 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"143 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d25a0aac6a5d99a82932b1cd59511fb4.pdf","sourceUrl":"https://www.se.com/eg/en/product/ENW24216/switch-disconnector-easypact-nw-1600a-h-4-poles-withdrawal/"},"ai":{"faq":[{"question":"What is the ENW24216 rated for in terms of current and voltage?","answer":"The ENW24216 is rated 1600 A operational current in AC-23A category at 690 V AC, with a rated insulation voltage of 1000 V AC and impulse withstand of 12 kV."},{"question":"What is the short-circuit withstand of the ENW24216?","answer":"It can withstand 66 kA for 1 second (36 kA for 3 seconds) and has a making capacity of 143 kA peak, all per IEC 60947-3."},{"question":"Where can I source the ENW24216?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24216","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24216 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}