{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24226","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24226","canonicalUrl":"https://aoctrl.com/schneider/ENW24226","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24226","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, switch disconnector, ENW25H, 2500 A AC-23A, 690 V, 4 poles, fixed mount, HA breaking capacity.","salesMarkdown":"The Schneider Electric ENW24226 is a fixed-mount switch disconnector from the EasyPact NW range, rated 2500 A in AC-23A duty at 690 V AC, 50/60 Hz. That AC-23A utilisation category means it is designed for switching motor loads and other highly inductive circuits — not just resistive isolation — and it carries a making capacity of 143 kA peak and a short-time withstand of 66 kA for 1 second per IEC 60947-3. The 4-pole configuration with neutral on the left suits distribution panels where a switched neutral is required, and the rear connection with a 115 mm pitch (without spreader) determines the busbar layout. The 2500 A continuous rating at 690 V is the headline number, but the AC-23A electrical endurance figures tell the real story for motor-switching applications: 5000 cycles at 440 V without maintenance, dropping to 2500 cycles at 690 V. If your duty cycle exceeds that, you will need to schedule maintenance or upsize. The mechanical durability is 20000 cycles with maintenance, 10000 without — both per IEC 60947-3. The HA breaking capacity code indicates a high interrupting rating, and the rated short-time withstand current of 66 kA for 1 second (36 kA for 3 seconds) gives the selectivity engineer headroom for coordination studies in high-fault-current panels. Pollution degree 4 per IEC 60664-1 is the most severe industrial classification — conductive dust or moisture bridging is expected. This switch disconnector is rated for that environment without derating, which is unusual for a device this size. The IP40 enclosure protection means it is not washdown-rated; it belongs in a clean, dry cabinet. Isolation suitability is confirmed per IEC 60947-3, with a visible contact position indicator. The rated insulation voltage is 1000 V AC, and impulse withstand is 12 kV. Fixed mounting on a base plate — no DIN rail. The dimensions are 537 mm wide by 352 mm high by 297 mm deep, so the enclosure must accommodate those clearances plus the rear connection depth. The connection pitch of 115 mm without spreader sets the busbar drilling pattern. Horizontal or vertical connection orientation is permitted, giving layout flexibility in the cabinet.","metaTitle":"Schneider Electric ENW24226 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24226 EasyPact NW switch disconnector, 2500A AC-23A, 690V, 4 poles, fixed mount. Active production. Quoted to order. IEC 60947-3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","title":"ENW24226","Height":"352 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 2500A, H, 4 Poles, fixed","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW25H","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Horizontal Vertical","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Breaking capacity code":"HA","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 2500 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"143 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/37ab0bb38ec5bf7c48c53bc75c96ba6d.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW24226/switch-disconnector-easypact-nw-2500a-h-4-poles-fixed/"},"ai":{"faq":[{"question":"What is the rated operational current of ENW24226?","answer":"The rated operational current (Ie) is 2500 A in AC-23A utilisation category at 690 V AC, 50/60 Hz per IEC 60947-3."},{"question":"What breaking capacity code does ENW24226 carry?","answer":"The breaking capacity code is HA, indicating a high interrupting rating. The rated short-time withstand current is 66 kA for 1 second and 36 kA for 3 seconds."},{"question":"Where can I buy ENW24226 and how is it quoted?","answer":"The ENW24226 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quotation."},{"question":"What standards does ENW24226 comply with?","answer":"It complies with IEC 60947-3 for switch-disconnectors, with isolation suitability confirmed. Pollution degree 4 per IEC 60664-1 is also specified."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24226","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24226 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}