{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24227","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24227","canonicalUrl":"https://aoctrl.com/schneider/ENW24227","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24227","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW series, ENW24227 switch disconnector, 3200 A AC-23A, 4 poles, fixed mount, breaking capacity code HA.","salesMarkdown":"Four poles, neutral on the left, rear-connected with a 115 mm pitch without spreader. Breaking capacity code HA means it is built for high-fault installations; the rated short-time withstand is 66 kA for 1 s (36 kA for 3 s), and the making capacity hits 143 kA peak at 50/60 Hz. AC-23A at 3200 A is the rating that governs real motor switching — this is not a resistive-load (AC-1) number. The electrical durability is specified at 5000 cycles at 440 V and 2500 cycles at 690 V without maintenance, so plan for periodic contact inspection in high-cycle applications. Mechanical durability is 20000 cycles with maintenance, 10000 without. IP40 enclosure protection keeps tools and fingers out but is not washdown-rated.","metaTitle":"ENW24227 EasyPact NW Switch Disconnector, 3200A, 4P","metaDescription":"Schneider Electric ENW24227 EasyPact NW switch disconnector, 3200A AC-23A, 4 poles, fixed mount. Active production. Quoted to order. IEC 60947-3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","title":"ENW24227","Height":"352 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 3200A, H, 4 Poles, fixed","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW32H","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Horizontal Vertical","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 5000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 2500 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Breaking capacity code":"HA","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 3200 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"66 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 36 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"143 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/9142e0fe62f7ee472e0b71f75c0d5832.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24227/switch-disconnector-easypact-nw-3200a-h-4-poles-fixed/"},"ai":{"faq":[{"question":"What is the closest alternative to ENW24227 in the EasyPact NW range?","answer":"The ENW24227 is a 3200 A, 4-pole, fixed-mount variant with breaking capacity code HA. Within the same EasyPact NW family, a lower-current or higher-breaking-capacity sibling would differ in the rated operational current (Ie) or the breaking capacity code; the form factor and mounting pattern are shared across the range, so a parametric substitute would need matching poles, mounting mode, and utilisation category."},{"question":"How do I get current pricing and availability for ENW24227?","answer":"Submit an RFQ through the storefront. The part is sourced and quoted to order, with availability and current pricing confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for ENW24227?","answer":"The ENW24227 is designed and tested to IEC 60947-3. It carries a rated insulation voltage of 1000 V AC and a rated impulse withstand voltage of 12 kV, with pollution degree 4 per IEC 60664-1. Specific RoHS, REACH, or UL documentation should be requested at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24227","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24227 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}