{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24241","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24241","canonicalUrl":"https://aoctrl.com/schneider/ENW24241","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24241","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW, fixed-mount circuit breaker, 2000 A at 40 °C, 4P, 50 kA Icu at 440 V AC, IEC 60947-2, IP40.","salesMarkdown":"The 50 kA Icu at 220...440 V AC (conforming to IEC 60947-2) is the maximum fault current it can safely interrupt once; the same 50 kA Ics rating means it can clear that fault and be reclosed without maintenance, which matters for service-entrance or feeder duty where a fault is rare but must not force a breaker swap. At 690 V the Icu drops to 42 kA — still substantial for 690 V distribution. The 4-pole (4P) design with neutral on the right handles three-phase plus neutral distribution. Rear vertical/horizontal connection pitch is 115 mm without spreader, so panel buswork or cable lugs need to match that spacing. IP40 enclosure protection means it is suitable for indoor switchboards — not washdown or outdoor exposure. Pollution degree 4 per IEC 60664-1 is the most severe industrial pollution class (conductive dust or wet conditions inside the enclosure), so this breaker is built for harsh environments inside a panel. ## Deployment context Fixed-mount on a base plate — this is a drawout-style breaker for switchboard or MCC installation, not a DIN-rail unit. The 537 mm width, 352 mm height, and 297 mm depth define the cutout and enclosure space; plan for rear connection access.","metaTitle":"Schneider Electric ENW24241 EasyPact NW Circuit Breaker, 200","metaDescription":"Schneider Electric ENW24241 EasyPact NW fixed-mount circuit breaker, 2000 A rated at 40 °C, 50 kA Icu at 440 V AC. IEC 60947-2, IP40. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","Height":"352 mm","Standards":"IEC 60947-2","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Right","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Breaking capacity":"50 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"ENW20N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","[In] rated current":"2000 A at 40 °C","Connection position":"Vertical Horizontal","Utilisation category":"Category B","Electrical durability":"Category B: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-2 Category B: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"N","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"2000 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ambient air temperature for operation":"-5...60 °C","[Ics] rated service breaking capacity":"50 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Icw] rated short-time withstand current":"50 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 42 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 25 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"105 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 88 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/24d189181d70df9875eba0348c6eedee.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW24241/circuit-breaker-frame-adapt-easypact-nw-4-poles-2000a-n-right-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24241/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24241","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24241 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}