{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24263","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24263","canonicalUrl":"https://aoctrl.com/schneider/ENW24263","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24263","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW ENW24263, switch disconnector, 1250 A AC-23A, 4 poles, drawout, right neutral, IP40.","salesMarkdown":"The Schneider Electric ENW24263 is a 4-pole switch disconnector from the EasyPact NW range, rated for 1250 A in AC-23A duty at 690 V AC. The 50 kA rated short-time withstand current (Icw) for 1 second tells you it can ride through a fault long enough for an upstream breaker to clear, which is the kind of coordination a distribution panel needs. It's built for continuous duty, drawout mounting on a rail, with rear vertical or horizontal connection positions. The 395 mm depth and 556 mm width give you the envelope for panel layout — this isn't a compact unit, it's a main breaker-sized disconnector for a switchboard. The headline number is 1250 A AC-23A at 690 V — that's the motor-switching current, not a resistive-heater rating. The 105 kA making capacity (Icm) means it can close onto a short-circuit without welding contacts, which is critical for a switch that may be called on to energize a faulted bus. That's unusual for a switch disconnector; most stop at PD3. The 12 kV impulse withstand voltage (Uimp) backs this up: it handles surge events common in industrial power systems without flashover. It's suitable for isolation per IEC 60947-3, with a visible contact position indicator. That means a qualified worker can verify the circuit is open by looking at the switch, not relying on a pilot light or meter. Drawout mounting on a rail means the switch can be racked out for maintenance or replacement without disconnecting the main bus bars — a standard feature for switchboard-grade disconnectors. The right-side neutral position and 115 mm connection pitch without spreader tell you the bus bar layout needs to match this footprint. IP40 protection means it's indoor-only, no washdown. The 6000-cycle electrical durability at 440 V and 4000 cycles at 690 V (AC-23A) gives a realistic service life for a main disconnector — not a daily-operating contactor, but fine for infrequent switching duty.","metaTitle":"ENW24263 EasyPact NW Switch Disconnector, 1250 A, 4 Poles","metaDescription":"Schneider Electric ENW24263 EasyPact NW switch disconnector. 1250 A AC-23A, 4 poles, drawout mount, IP40. Active production, sourced to order against RFQ. IEC 60947-3.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"556 mm","title":"ENW24263","Height":"439 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 1250A, N, 4 Poles, right, withdrawal","Control type":"Push-button","Network type":"AC","Mounting mode":"Drawout","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail","Neutral position":"Right","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW12N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Vertical Horizontal","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 1250 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"105 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/cbb75df39482f9f616b8f60fbfa47715.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24263/switch-disconnector-easypact-nw-1250a-n-4-poles-right-withdrawal/"},"ai":{"faq":[{"question":"What is the key rating that decides fit for this switch disconnector?","answer":"The 1250 A AC-23A rating at 690 V is the load-switching current for motor circuits. The 50 kA Icw for 1 second tells you the fault-withstand capability for coordination with upstream protection."},{"question":"Where can I buy ENW24263 and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent industrial distribution. Availability and current pricing are confirmed at quote time."},{"question":"What standards does ENW24263 comply with?","answer":"It complies with IEC 60947-3 for switch-disconnectors, with pollution degree 4 per IEC 60664-1 and a 12 kV impulse withstand voltage."},{"question":"What is the depth of ENW24263?","answer":"The depth is 395 mm, with a width of 556 mm and height of 439 mm. This is a full-size switchboard disconnector, not a panel-mount compact unit."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24263","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24263 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}