{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24271","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24271","canonicalUrl":"https://aoctrl.com/schneider/ENW24271","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24271","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW switch disconnector, ENW24271, 1250 A AC-23A, 4 poles, fixed mount, IP40, IEC 60947-3.","salesMarkdown":"The Schneider Electric ENW24271 is a switch disconnector in the EasyPact NW range, rated for 1250 A in AC-23A duty at 690 V AC. Four poles, neutral on the right, fixed mounting on a base plate. The rear connection pitch is 115 mm without a spreader. Rated operational current is 1250 A in AC-23A at 690 V. That's the motor-switching current, not the resistive-heating rating — if you're feeding a bank of heaters at unity power factor, the part will handle more, but for motor loads this is your hard ceiling. Continuous duty rated, so no derating for sustained on-time. Short-time withstand (Icw) is 50 kA for 1 second, or 25 kA for 3 seconds. That tells you the disconnector can ride through a fault long enough for an upstream breaker to clear — critical for selective coordination in a distribution board. Short-circuit making capacity (Icm) is 105 kA peak, meaning it can close onto an existing fault without welding contacts. Impulse withstand voltage is 12 kV, and pollution degree 4 per IEC 60664-1 — that's the heavy-industrial rating for conductive dust or condensation inside the enclosure. If your panel lives in a cement plant or a paper mill, that matters more than the IP rating. Electrical durability at 440 V AC is 6,000 cycles; at 690 V it drops to 4,000 cycles. That's typical for a high-current AC-23A switch — plan your maintenance intervals around the 690 V figure if that's your line voltage.","metaTitle":"ENW24271 EasyPact NW Switch Disconnector, 1250A, 4 Poles","metaDescription":"Schneider Electric ENW24271 EasyPact NW switch disconnector, 1250 A AC-23A, 4 poles, IP40, IEC 60947-3. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"537 mm","title":"ENW24271","Height":"352 mm","Standards":"IEC 60947-3","Rated duty":"Continuous","description":"switch disconnector, EasyPact NW, 1250A, N, 4 Poles, right, fixed","Control type":"Push-button","Network type":"AC","Mounting mode":"Fixed","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Base plate","Neutral position":"Right","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact NW","Device short name":"ENW12N","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","Connection position":"Vertical Horizontal","Utilisation category":"AC-23A","Electrical durability":"AC-23A: 6000 cycles 440 V AC 50/60 Hz without maintenance conforming to IEC 60947-3 AC-23A: 4000 cycles 690 V AC 50/60 Hz without maintenance conforming to IEC 60947-3","Mechanical durability":"20000 cycles with maintenance conforming to IEC 60947-3 10000 cycles without maintenance conforming to IEC 60947-3","Location of connection":"Rear","IP degree of protection":"IP40","Product or component type":"Switch disconnector","Suitability for isolation":"Yes conforming to IEC 60947-3","Contact position indicator":"Yes","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-3","[Ie] rated operational current":"AC-23A: 1250 A AC 50/60 Hz 690 V","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","Ambient air temperature for storage":"-40...85 °C without control unit","Ambient air temperature for operation":"-5...70 °C","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-3","[Icw] rated short-time withstand current":"50 kA during 1 s conforming to IEC 60947-3 at -5...70 °C 25 kA during 3 s conforming to IEC 60947-3 at -5...70 °C","[Icm] rated short-circuit making capacity":"105 kA AC at 50/60 Hz"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/90421a072507923de447e3a0b5f3f4fd.pdf","sourceUrl":"https://www.se.com/ae/en/product/ENW24271/switch-disconnector-easypact-nw-1250a-n-4-poles-right-fixed/"},"ai":{"faq":[{"question":"What is the rated operational current of ENW24271?","answer":"1250 A in AC-23A utilisation category at 690 V AC, 50/60 Hz."},{"question":"Where can I buy ENW24271 and how is it quoted?","answer":"The ENW24271 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at the time of quote."},{"question":"What standards does ENW24271 comply with?","answer":"It complies with IEC 60947-3 for switch-disconnectors and IEC 60664-1 for insulation coordination at pollution degree 4."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24271","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24271 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}