{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"ENW24273","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"ENW24273","canonicalUrl":"https://aoctrl.com/schneider/ENW24273","factsUrl":"https://aoctrl.com/api/mcp/products/ENW24273","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact NW switch disconnector, ENW24273, 2000 A AC-23A, 4 poles, fixed mount, IP40.","salesMarkdown":"## What the 2000 A AC-23A rating means for your load The Schneider Electric ENW24273 is a 4-pole switch disconnector from the EasyPact NW range, rated 2000 A in AC-23A duty at 690 V. AC-23A covers switching of motor loads and other highly inductive circuits — this is not a general-purpose resistive-load switch. The 2000 A figure governs the maximum operational current for making and breaking motor circuits, so it is sized for large distribution or motor-control centre incomers, not branch circuits. Rated short-time withstand (Icw) is 50 kA for 1 s and 25 kA for 3 s, which means the disconnector can ride through a fault long enough for an upstream protective device to clear — critical for selective coordination in a switchboard. The short-circuit making capacity (Icm) of 105 kA AC confirms it can close onto a bolted fault without welding contacts. ## Isolation and environmental fit The ENW24273 is certified for isolation per IEC 60947-3, with a clearly marked contact-position indicator and a rated impulse withstand voltage of 12 kV. IP40 protection keeps tools and fingers out but does not seal against water; mount it inside a cabinet if washdown is present. Fixed mounting on a base plate, rear connection, neutral on the right, and a 115 mm connection pitch without spreader. The 537 mm width and 352 mm height mean it needs a generous backplate cutout — verify your enclosure door swing clears the handle travel before committing the BOM.","metaTitle":"Schneider Electric ENW24273 EasyPact NW Switch Disconnector,","metaDescription":"Schneider Electric ENW24273 EasyPact NW switch disconnector, 2000 A rated operational current AC-23A, 4 poles, IP40. Active production. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"297 mm","Width":"537 mm","Height":"352 mm","Current":"AC-23 A: 2000 A AC 50/60 Hz 690 V","Voltage":"690 V AC 50/60 Hz conforming to IEC 60947-3","IP Rating":"IP40","Application":"Distribution","Control Type":"Push-button","Product Status":"Active","Terminal Pitch":"115 mm without spreader","Pollution Degree":"4 conforming to IEC 60664-1","Temp Storage Max":"85 °C","Temp Storage Min":"-40 °C","Insulation Voltage Ui":"1000 V AC 50/60 Hz conforming to IEC 60947-3","Temp Operating Max":"70 °C","Temp Operating Min":"-5 °C","Temperature Storage":"-40...85 °C without control unit","Utilization Category":"AC-23 A","Main Product Or Component Type":"Switch disconnector","Ambient Air Temperature Operation":"-5...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/78e5a24cfc7543496a12879cfd5ed7c4.pdf","sourceUrl":"https://www.se.com/in/en/product/ENW24273/switch-disconnector-easypact-nw-2000a-n-4-poles-right-fixed/","alternativesUrl":"https://aoctrl.com/api/mcp/products/ENW24273/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/ENW24273","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/ENW24273 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}