{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EVS16H3MF60","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EVS16H3MF60","canonicalUrl":"https://aoctrl.com/schneider/EVS16H3MF60","factsUrl":"https://aoctrl.com/api/mcp/products/EVS16H3MF60","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EVS, EVS16H3MF60, 3-pole circuit breaker, 1600 A, 65 kA Icu at 440 V AC, electronic trip unit EVS Trip System6.0, fixed mounting.","salesMarkdown":"The Schneider Electric EVS16H3MF60 is a 3-pole fixed-mount circuit breaker from the EasyPact EVS range, rated 1600 A at 40 °C and built to IEC 60947-2 for distribution duty. It carries a 65 kA Icu breaking capacity at 220–440 V AC and 50 kA at 690 V AC — that's the maximum fault current it can safely interrupt without damage, which sets the upstream fault level the panel must be rated for. At 422 mm wide, 352 mm high, and 297 mm deep, this breaker needs a dedicated compartment in the switchboard — it's not a DIN-rail unit. Mounting is fixed to a rail or base plate, with rear vertical or horizontal connection at a 115 mm pitch without spreader. IP40 front face keeps tools and fingers out but doesn't seal against water — keep it indoors or in a weatherproof enclosure. ## What the standards tell you IEC 60947-2 is the standard for low-voltage circuit breakers — it covers the breaking capacity, utilization category, and isolation suitability. This breaker is marked Category B, meaning it's a selective breaker with intentional short-time delay for coordination downstream. Suitability for isolation is certified per the same standard, so it can be used as a visible-break disconnecting means. ## Durability and response Mechanical endurance is 20,000 cycles with maintenance and 10,000 without; electrical endurance is 5,000 cycles at 440/690 V AC without maintenance per IEC 60947-2. Maximum breaking time is 25 ms, and closing response is 70 ms — fast enough to limit let-through energy on a fault. The contact position indicator gives a visual open/closed state, and the fault indication shows internal fault, overload, short-circuit, or earth fault on the trip unit display.","metaTitle":"Schneider Electric EVS16H3MF60 EasyPact EVS Circuit Breaker,","metaDescription":"Schneider Electric EVS16H3MF60 EasyPact EVS 3-pole circuit breaker. 1600 A rated current, 65 kA breaking capacity at 440 V AC. IEC 60947-2. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"422 mm","Height":"352 mm","Standards":"IEC 60947-2","Control type":"Manually operated","Network type":"AC","Mounting mode":"Fixed","Thermal memory":"20 minutes before and after tripping","Trip unit name":"EVS Trip System6.0","Protection type":"Overload protection (long time) Instantaneous short-circuit protection Short time short-circuit protection Earth fault","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Fault indication":"Internal fault Overload Short-circuit Earth fault","Mounting support":"Rail Base plate","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact EVS","Trip unit rating":"1600 A","Breaking capacity":"65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"EVS16H","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"1600 A at 40 °C","Connection position":"Vertical Horizontal","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"H","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"1600 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 9 settings","Zone selective interlocking ZSI":"With","Short-time delay adjustment type":"Adjustable 5 settings","Long time pick-up adjustment range":"0.4...1 x In","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ground-fault pick-up adjustment type":"Adjustable 9 settings","Long time pick-up adjustment type Ir":"Adjustable 9 settings","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s at 6 x Ir","Instantaneous pick-up adjustment range":"2...15 x In Off","Short-time pick-up adjustment type Isd":"Adjustable 9 settings","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Tsd] Short-Time Delay Adjustment Range":"100...400 ms","Instantaneous pick-up adjustment type Ii":"Adjustable 9 settings","[Icw] rated short-time withstand current":"65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] short-time pick-up adjustment range":"1.5...10 x Ir","[Ig] ground-fault pick-up adjustment range":"0.2...1 x In","Ground-fault time delay adjustment type -tg":"Adjustable 5 settings","[Tg] Ground-Fault Time Delay Adjustment Range":"100...400 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/077a5f1941aaf04f9a26eb29891e0a47.pdf","sourceUrl":"https://www.se.com/vn/en/product/EVS16H3MF60/easypact-evs-1600a-65ka-3p-mf-trip-system6-0-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EVS16H3MF60/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the EVS16H3MF60?","answer":"65 kA Icu at 220–440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. That's the maximum fault current the breaker can safely interrupt at those voltages."},{"question":"Where can I buy the EVS16H3MF60?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or price is listed here."},{"question":"What protection functions does the EVS Trip System6.0 provide?","answer":"Overload protection (long time), instantaneous short-circuit protection, short-time short-circuit protection, and earth-fault protection. It also has a 20-minute thermal memory before and after tripping."},{"question":"What are the mounting dimensions of the EVS16H3MF60?","answer":"422 mm wide, 352 mm high, and 297 mm deep. It mounts fixed to a rail or base plate with rear connection at a 115 mm pitch without spreader."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EVS16H3MF60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EVS16H3MF60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}