{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EVS16H3MW60","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EVS16H3MW60","canonicalUrl":"https://aoctrl.com/schneider/EVS16H3MW60","factsUrl":"https://aoctrl.com/api/mcp/products/EVS16H3MW60","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EVS, drawout circuit breaker, EVS16H3MW60, 1600 A, 65 kA Icu at 440 V AC, 3-pole, electronic trip unit EVS Trip System6.0.","salesMarkdown":"## What this 1600 A drawout breaker does on the line The Schneider Electric EVS16H3MW60 is a 1600 A drawout circuit breaker from the EasyPact EVS range, built for distribution duty in industrial switchgear. It carries a 65 kA Icu at 220…440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2 — enough to handle high-fault utility feeds without cascading upstream. The electronic EVS Trip System6.0 unit gives you overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection, all adjustable. ## Mounting and panel fit — drawout frame, rear connection Drawout mounting means the breaker slides into a cradle on a rail or base plate — no hard wiring to the breaker body, so swap-out is a racking handle and a few minutes. Rear vertical or horizontal connection at 115 mm pitch without spreader. Dimensions: 441 mm wide, 439 mm tall, 395 mm deep. IP40 on the front, pollution degree 4 per IEC 60664-1 for harsh environments. Contact position indicator is visible through the door. ## Durability and duty cycle — Category B, 5000 electrical cycles Electrical durability: 5000 cycles at 440/690 V AC without maintenance. Mechanical: 20,000 cycles with maintenance, 10,000 without. Maximum breaking time 25 ms, maximum closing time 70 ms. Suitability for isolation is marked yes per the same standard.","metaTitle":"Schneider EVS16H3MW60 EasyPact Circuit Breaker, 1600 A, 65 k","metaDescription":"Schneider Electric EVS16H3MW60 EasyPact EVS drawout circuit breaker. 1600 A rated current, 65 kA Icu at 440 V AC. IEC 60947-2, Category B. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"441 mm","Height":"439 mm","Standards":"IEC 60947-2","Control type":"Manually operated","Network type":"AC","Mounting mode":"Drawout","Thermal memory":"20 minutes before and after tripping","Trip unit name":"EVS Trip System6.0","Protection type":"Overload protection (long time) Instantaneous short-circuit protection Short time short-circuit protection Earth fault","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Fault indication":"Internal fault Overload Short-circuit Earth fault","Mounting support":"Rail Base plate","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact EVS","Trip unit rating":"1600 A","Breaking capacity":"65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"EVS16H","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"1600 A at 40 °C","Connection position":"Vertical Horizontal","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"H","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"1600 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 9 settings","Zone selective interlocking ZSI":"With","Short-time delay adjustment type":"Adjustable 5 settings","Long time pick-up adjustment range":"0.4...1 x In","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ground-fault pick-up adjustment type":"Adjustable 9 settings","Long time pick-up adjustment type Ir":"Adjustable 9 settings","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s at 6 x Ir","Instantaneous pick-up adjustment range":"2...15 x In Off","Short-time pick-up adjustment type Isd":"Adjustable 9 settings","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Tsd] Short-Time Delay Adjustment Range":"100...400 ms","Instantaneous pick-up adjustment type Ii":"Adjustable 9 settings","[Icw] rated short-time withstand current":"65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] short-time pick-up adjustment range":"1.5...10 x Ir","[Ig] ground-fault pick-up adjustment range":"0.2...1 x In","Ground-fault time delay adjustment type -tg":"Adjustable 5 settings","[Tg] Ground-Fault Time Delay Adjustment Range":"100...400 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/97aca64c3315b05cb5651616f73ead3c.pdf","sourceUrl":"https://www.se.com/vn/en/product/EVS16H3MW60/easypact-evs-1600a-65ka-3p-mdo-trip-system6-0-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EVS16H3MW60/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the EVS16H3MW60?","answer":"65 kA Icu at 220…440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2."},{"question":"What protection functions does the EVS Trip System6.0 provide?","answer":"Overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection."},{"question":"Where can I buy the EVS16H3MW60 and how is it quoted?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What compliance documentation does Schneider provide for this breaker?","answer":"The breaker is designed and tested to IEC 60947-2. Schneider typically provides a Declaration of Conformity and test reports upon request through the supply channel."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EVS16H3MW60","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EVS16H3MW60 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}