{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EVS20H4MW6A","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EVS20H4MW6A","canonicalUrl":"https://aoctrl.com/schneider/EVS20H4MW6A","factsUrl":"https://aoctrl.com/api/mcp/products/EVS20H4MW6A","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EVS, EVS20H4MW6A, drawout circuit breaker, 4P, 2000 A, 65 kA Icu at 440 V AC, electronic trip unit, IP40.","salesMarkdown":"The EVS20H4MW6A is a 4-pole drawout circuit breaker from the EasyPact EVS range, rated 2000 A continuous at 40 °C with an electronic trip unit (EVS Trip System6A). IEC 60947-2 Category B utilisation confirms it is designed for selectivity (discrimination) with downstream breakers, so a fault on a branch clears without tripping this main breaker. ## Drawout mounting and panel integration Drawout mounting means the breaker slides in and out of a fixed cradle — no need to disconnect power cables for removal or replacement. This is standard for main breakers where uptime matters: pull the breaker for maintenance or swap without de-energising the bus. Mounting support is a rail or base plate; connection is rear with a 115 mm pitch without spreader. Vertical or horizontal connection orientation gives flexibility in cabinet layout. Dimensions: 556 mm wide × 439 mm high × 395 mm deep — verify the cubicle depth before specifying. ## Protection and trip unit The electronic trip unit provides overload (long-time), instantaneous short-circuit, short-time short-circuit, and earth-fault protection. The 20-minute thermal memory means the trip curve accounts for prior heating — important when re-energising after a fault, preventing nuisance trips on a still-hot cable. Fault indication covers internal fault, overload, short-circuit, and earth fault on the digital display. Maximum breaking time is 25 ms — fast enough to limit let-through energy for downstream equipment.","metaTitle":"Schneider Electric EVS20H4MW6A EasyPact EVS Circuit Breaker,","metaDescription":"Schneider Electric EVS20H4MW6A EasyPact EVS drawout circuit breaker. 2000 A rated current, 65 kA breaking capacity at 440 V AC. IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"556 mm","Height":"439 mm","Standards":"IEC 60947-2","Control type":"Manually operated","Display type":"Digital display","Network type":"AC","Mounting mode":"Drawout","Thermal memory":"20 minutes before and after tripping","Trip unit name":"EVS Trip System6A","Protection type":"Overload protection (long time) Instantaneous short-circuit protection Short time short-circuit protection Earth fault","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Fault indication":"Internal fault Overload Short-circuit Earth fault","Mounting support":"Rail Base plate","Neutral position":"Left","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact EVS","Trip unit rating":"2000 A","Breaking capacity":"65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"EVS20H","Network frequency":"50/60 Hz","Poles description":"4P","Device application":"Distribution","[In] rated current":"2000 A at 40 °C","Connection position":"Vertical Horizontal","Type of measurement":"Current","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"H","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"2000 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Neutral protection setting":"Without protection 0.5 x Ir 1 x Ir","Protected poles description":"4P 4d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LSIG","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 9 settings","Zone selective interlocking ZSI":"With","Short-time delay adjustment type":"Adjustable 5 settings","Long time pick-up adjustment range":"0.4...1 x In","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Ground-fault pick-up adjustment type":"Adjustable 9 settings","Long time pick-up adjustment type Ir":"Adjustable 9 settings","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s at 6 x Ir","Instantaneous pick-up adjustment range":"2...15 x In Off","Short-time pick-up adjustment type Isd":"Adjustable 9 settings","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","[Tsd] Short-Time Delay Adjustment Range":"100...400 ms","Instantaneous pick-up adjustment type Ii":"Adjustable 9 settings","[Icw] rated short-time withstand current":"65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Isd] short-time pick-up adjustment range":"1.5...10 x Ir","[Ig] ground-fault pick-up adjustment range":"0.2...1 x In","Ground-fault time delay adjustment type -tg":"Adjustable 5 settings","[Tg] Ground-Fault Time Delay Adjustment Range":"100...400 ms"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fbd03ba6a4775dc1cf1be35eabfca6f3.pdf","sourceUrl":"https://www.se.com/vn/en/product/EVS20H4MW6A/easypact-evs-2000a-65ka-4p-mdo-trip-system6-0a-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EVS20H4MW6A/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of the EVS20H4MW6A?","answer":"65 kA Icu at 220...440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. The 'H' in the short name EVS20H indicates the high breaking capacity code."},{"question":"Where can I buy the EVS20H4MW6A and get current pricing?","answer":"Sourced and quoted to order against an RFQ through independent industrial-automation distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What is the closest alternative to the EVS20H4MW6A in the EasyPact EVS family?","answer":"Within the same EasyPact EVS range, the closest peer is the equivalent frame size with a different trip unit rating or breaking capacity code. The EVS20H4MW6A uses the EVS Trip System6A electronic trip unit rated 2000 A with 'H' breaking capacity. A lower-current variant or a different trip unit type would change the protection curve and interrupting rating — verify the specific BOM requirements before substituting."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EVS20H4MW6A","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EVS20H4MW6A when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}