{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EVS25H3MW20","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EVS25H3MW20","canonicalUrl":"https://aoctrl.com/schneider/EVS25H3MW20","factsUrl":"https://aoctrl.com/api/mcp/products/EVS25H3MW20","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EVS, EVS25H3MW20, 3-pole drawout circuit breaker, 2500 A rated current, 65 kA Icu at 440 V AC, IEC 60947-2.","salesMarkdown":"It carries a 2500 A rated current at 40 °C and a 65 kA Icu breaking capacity at 220…440 V AC, per IEC 60947-2. The EVS Trip System2.0 is an electronic trip unit rated at 2500 A, with LI protection — overload (long-time) and instantaneous short-circuit. That matters on a motor feeder or a welder circuit where repeated starts can cook the cable if the breaker doesn't account for prior heating. This is a drawout breaker — it mounts on a rail base plate, with rear vertical or horizontal connections. The 115 mm connection pitch (without spreader) and the 441 mm width, 439 mm height, 395 mm depth give you the envelope for panel layout. IP40 protection means it's fine inside a clean indoor switchboard but not for washdown environments. Pollution degree 4 per IEC 60664-1 tells you it's rated for harsh conductive environments — think industrial atmospheres with dust or condensation. Electrical durability is 5,000 cycles at 440/690 V AC without maintenance. That electrical figure is Category B per IEC 60947-2, meaning the breaker is designed for selective coordination — it can hold in during a downstream fault to let a branch breaker clear first. Rated insulation voltage (Ui) is 1000 V AC. Breaking capacity is 65 kA Icu at 220…440 V AC, and 50 kA Icu at 690 V AC. Maximum breaking time is 25 ms, maximum closing response time is 70 ms. The 3-pole, 3-protected-poles (3d) configuration means all three poles have the same protection — no solid-neutral variant here.","metaTitle":"Schneider Electric EVS25H3MW20 EasyPact Circuit Breaker, 250","metaDescription":"Schneider Electric EVS25H3MW20 EasyPact EVS drawout circuit breaker. 2500 A rated current, 65 kA breaking capacity at 440 V AC. IEC 60947-2. Current lifecycle stage. Available to o","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"395 mm","Range":"EasyPact","Width":"441 mm","Height":"439 mm","Standards":"IEC 60947-2","Control type":"Manually operated","Network type":"AC","Mounting mode":"Drawout","Thermal memory":"20 minutes before and after tripping","Trip unit name":"EVS Trip System2.0","Protection type":"Overload protection (long time) Instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact EVS","Trip unit rating":"2500 A","Breaking capacity":"65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"EVS25H","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"2500 A at 40 °C","Connection position":"Vertical Horizontal","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"H","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"2500 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 9 settings","Zone selective interlocking ZSI":"With","Long time pick-up adjustment range":"0.4...1 x In","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Long time pick-up adjustment type Ir":"Adjustable 9 settings","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s at 6 x Ir","Instantaneous pick-up adjustment range":"1.5...10 x Ir","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","Instantaneous pick-up adjustment type Ii":"Adjustable 9 settings","[Icw] rated short-time withstand current":"65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0f499e47f62e490e6429e5a68704644e.pdf","sourceUrl":"https://www.se.com/vn/en/product/EVS25H3MW20/easypact-evs-2500a-65ka-3p-mdo-trip-system2-0-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EVS25H3MW20/alternatives.json"},"ai":{"faq":[{"question":"What is the EVS25H3MW20 breaking capacity?","answer":"65 kA Icu at 220…440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2."},{"question":"What trip unit does the EVS25H3MW20 use?","answer":"It uses the electronic EVS Trip System2.0 with LI protection (overload and instantaneous short-circuit), rated 2500 A."},{"question":"What standards does the EVS25H3MW20 comply with?","answer":"It complies with IEC 60947-2, and its pollution degree is 4 per IEC 60664-1."},{"question":"Where can I buy the EVS25H3MW20 and how is it quoted?","answer":"It is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EVS25H3MW20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EVS25H3MW20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}