{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EVS25H3NF20","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EVS25H3NF20","canonicalUrl":"https://aoctrl.com/schneider/EVS25H3NF20","factsUrl":"https://aoctrl.com/api/mcp/products/EVS25H3NF20","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EVS, EVS25H3NF20, 3P circuit breaker, 2500 A at 40 °C, 65 kA Icu at 440 V AC, electronically controlled, fixed mount.","salesMarkdown":"The Schneider Electric EVS25H3NF20 is a 3-pole EasyPact EVS circuit breaker rated for 2500 A at 40 °C, with a 65 kA Icu breaking capacity at 220…440 V AC and 50 kA at 690 V AC per IEC 60947-2. It uses an electronic EVS Trip System2.0 trip unit providing overload (long-time) and instantaneous short-circuit protection. The electronic trip unit allows adjustment of the long-time pickup and delay, plus an instantaneous setting — the 20-minute thermal memory before and after tripping prevents nuisance reclosure on a hot conductor. Category B utilisation means the breaker is intended for distribution with no specific short-time delay requirement, and it carries 5000 electrical cycles without maintenance at 440/690 V. Pollution degree 4 per IEC 60664-1 means the breaker is rated for continuous conductive contamination (e.g., dust with moisture), so it can be placed in industrial panels without sealed enclosures. Suitability for isolation per IEC 60947-2 means the open contacts provide a visible disconnect gap — no separate isolator needed downstream. ## Integration notes Electrically operated — the closing coil draws from the control circuit. Maximum closing response time is 70 ms; maximum breaking time is 25 ms. The contact position indicator is visible on the front of the breaker for local status checks.","metaTitle":"Schneider Electric EVS25H3NF20 EasyPact Circuit Breaker, 250","metaDescription":"Schneider Electric EVS25H3NF20 EasyPact EVS circuit breaker. 2500 A rated current, 65 kA Icu at 440 V. IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Air Circuit Breakers"],"specifications":{"Depth":"297 mm","Range":"EasyPact","Width":"422 mm","Height":"352 mm","Standards":"IEC 60947-2","Control type":"Electrically operated","Network type":"AC","Mounting mode":"Fixed","Product weight":"60 kg","Thermal memory":"20 minutes before and after tripping","Trip unit name":"EVS Trip System2.0","Protection type":"Overload protection (long time) Instantaneous short-circuit protection","lifecycle_stage":"current","Connection pitch":"115 mm without spreader","Mounting support":"Rail Base plate","Pollution degree":"4 conforming to IEC 60664-1","Range of product":"EasyPact EVS","Trip unit rating":"2500 A","Breaking capacity":"65 kA Icu at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"EVS25H","Network frequency":"50/60 Hz","Poles description":"3P","Device application":"Distribution","[In] rated current":"2500 A at 40 °C","Connection position":"Vertical Horizontal","Trip unit technology":"Electronic","Utilisation category":"Category B","Electrical durability":"Category B: 5000 cycles 440/690 V AC 50/60 Hz without maintenance conforming to IEC 60947-2","Maximum breaking time":"25 ms","Mechanical durability":"20000 cycles (with maintenance) conforming to IEC 60947-2 10000 cycles (without maintenance) conforming to IEC 60947-2","Breaking capacity code":"H","Location of connection":"Rear","IP degree of protection":"IP40","Circuit breaker CT rating":"2500 A","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Contact position indicator":"Yes","Protected poles description":"3P 3d","Maximum closing response time":"70 ms","[Ui] rated insulation voltage":"1000 V AC 50/60 Hz conforming to IEC 60947-2","Trip unit protection functions":"LI","[Ue] rated operational voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","Long time delay adjustment type":"Adjustable 9 settings","Zone selective interlocking ZSI":"With","Long time pick-up adjustment range":"0.4...1 x In","Ambient air temperature for storage":"-40...85 °C without control unit -25...85 °C with control unit","Long time pick-up adjustment type Ir":"Adjustable 9 settings","Ambient air temperature for operation":"-5...70 °C","[Ics] rated service breaking capacity":"65 kA (Ics) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (Ics) at 690 V AC 50/60 Hz conforming to IEC 60947-2","[Tr] Long-Time Delay Adjustment Range":"0.5...24 s at 6 x Ir","Instantaneous pick-up adjustment range":"1.5...10 x Ir","[Uimp] rated impulse withstand voltage":"12 kV conforming to IEC 60947-2","Instantaneous pick-up adjustment type Ii":"Adjustable 9 settings","[Icw] rated short-time withstand current":"65 kA (1 s) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA (1 s) at 690 V AC 50/60 Hz conforming to IEC 60947-2 36 kA (3 s) at 440/690 V AC 50/60 Hz conforming to IEC 60947-2","[Icm] rated short-circuit making capacity":"143 kA (Icm) at 220...440 V AC 50/60 Hz conforming to IEC 60947-2 105 kA (Icm) at 690 V AC 50/60 Hz conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d6f78a7f7a816904a732c8fce310c656.pdf","sourceUrl":"https://www.se.com/vn/en/product/EVS25H3NF20/easypact-evs-2500a-65ka-3p-ef-240vac-trip-system2-0-circuit-breaker/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EVS25H3NF20/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy the EVS25H3NF20 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — submit an RFQ for a firm commercial offer."},{"question":"What is the breaking capacity of the EVS25H3NF20?","answer":"It has a 65 kA Icu at 220…440 V AC and 50 kA Icu at 690 V AC, both per IEC 60947-2. The H breaking capacity code indicates this is the high-interrupt version of the EVS25 frame."},{"question":"What protection does the EVS Trip System2.0 provide?","answer":"The electronic trip unit provides overload protection (long-time) and instantaneous short-circuit protection. It includes a 20-minute thermal memory before and after tripping to prevent reclosure on a hot conductor."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EVS25H3NF20","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EVS25H3NF20 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}