{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZ9R62263","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZ9R62263","canonicalUrl":"https://aoctrl.com/schneider/EZ9R62263","factsUrl":"https://aoctrl.com/api/mcp/products/EZ9R62263","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric Easy9 EZ9R62263, Residual Current Circuit Breaker (RCCB), 2P, 63 A, AC type, 300 mA, IEC 61008-1.","salesMarkdown":"The Schneider Electric EZ9R62263 is a 2-pole residual current circuit breaker (RCCB) from the Easy9 range, rated 63 A with 300 mA earth-leakage sensitivity, Type AC (trips on sinusoidal AC fault currents). This part is officially obsolete per the manufacturer. No successor order code is listed in the available records. Rated operational voltage is 230 V AC at 50 Hz, with a breaking and making capacity of 630 A at 230 V per IEC 61008-1. The conditional short-circuit current is 6000 A — meaning the device can withstand a fault up to 6 kA if backed by an upstream overcurrent protective device sized per the standard. Rated impulse withstand voltage is 4 kV, which covers typical transient overvoltages in residential distribution. The tunnel-type terminals accept 1–35 mm² rigid or 1–25 mm² flexible cable, torqued to 3.5 N·m. IP20 on the body, IP40 when enclosed in a modular enclosure — standard for indoor panel installation. The part is tropicalised per IEC 60068-2-30 (damp heat cyclic), which matters for high-humidity environments. Mounts on DIN rail via clip-on mechanism. Occupies 4 modules of 9 mm pitch (36 mm width). Neutral is on the left. The toggle control provides a contact-position indicator. Tightening torque of 3.5 N·m on the tunnel terminals — use a torque screwdriver to avoid terminal damage.","metaTitle":"Schneider Electric EZ9R62263 Easy9 RCCB, 2P, 63A, 300mA, AC","metaDescription":"Schneider Electric EZ9R62263 Easy9 RCCB, 2-pole, 63 A, 300 mA sensitivity, Type AC. Obsolete — sourced to order against RFQ. IEC 61008-1.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":["Residual Current Breakers (RCCB/RCBO)"],"specifications":{"Depth":"73 mm","Poles":"2P","Range":"Easy9","Width":"36 mm","Height":"81 mm","Standards":"IEC 61008-1","9 Mm Pitches":"4","Control type":"Toggle","Network type":"AC","Mounting mode":"Clip-on","Market segment":"Residential","Tropicalisation":"2 conforming to IEC 60068-2-30","lifecycle_stage":"current","Mounting support":"DIN rail","Neutral position":"Left","Targeted country":"Albania Kosovo Macedonia","Network frequency":"50/60 Hz","Relative humidity":"95 % at 55 °C","Tightening torque":"3.5 N.m top or bottom","Device application":"Protection","[In] rated current":"63 A","Electrical durability":"4000 cycles","Mechanical durability":"10000 cycles","Connections - terminals":"Tunnel type terminal (top or bottom) 1...35 mm² rigid Tunnel type terminal (top or bottom) 1...25 mm² flexible","IP degree of protection":"IP20 IP40 (modular enclosure)","Device location in system":"Outgoer","Earth-leakage sensitivity":"300 mA","Product or component type":"Residual current circuit breaker (RCCB)","Contact position indicator":"Yes","Earth-leakage protection class":"Type AC","[Ue] rated operational voltage":"230 V AC 50 Hz","Rated breaking and making capacity":"630 A 230 V conforming to IEC 61008-1","Ambient air temperature for storage":"-40...85 °C","Earth-leakage protection time delay":"Instantaneous","Ambient air temperature for operation":"-5...60 °C","[Uimp] rated impulse withstand voltage":"4 kV","Rated conditional short-circuit current":"6000 A"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c96c0fa6c0595965a49dccf54913de29.pdf","sourceUrl":"https://www.se.com/ng/en/product/EZ9R62263/residual-current-circuit-breaker-rccb-easy9-2p-63a-ac-type-300ma/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZ9R62263/alternatives.json"},"ai":{"faq":[{"question":"Where can I buy EZ9R62263?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What are the key ratings of EZ9R62263?","answer":"It is a 2-pole RCCB rated 63 A, 300 mA sensitivity, Type AC, 230 V AC, with a conditional short-circuit current of 6000 A and impulse withstand of 4 kV."},{"question":"What is the depth of EZ9R62263?","answer":"The depth is 73 mm."},{"question":"What standards does EZ9R62263 comply with?","answer":"It complies with IEC 61008-1 and is tropicalised per IEC 60068-2-30."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZ9R62263","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZ9R62263 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}