{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100F3025","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100F3025","canonicalUrl":"https://aoctrl.com/schneider/EZC100F3025","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100F3025","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100F, 3-pole MCCB, 25 A thermal-magnetic TM-D trip unit, 25 kA Icu at 240 V AC, fixed mount, front connections, IP20, IEC 60947-2.","salesMarkdown":"## MCCB for distribution panels — the key ratings that govern fit Its 25 A thermal-magnetic TM-D trip unit provides both short-circuit and overload protection in a single device, with a rated insulation voltage of 690 V AC and a maximum operational voltage of 550 V AC (50/60 Hz) or 250 V DC. At 400–415 V AC the Icu drops to 10 kA, and at 550 V AC to 5 kA, so the voltage at the point of installation directly governs the available fault current the breaker can interrupt. ## Thermal-magnetic trip and environmental limits Mechanical durability is rated at 13,000 cycles. ## Mounting and connection The connection pitch is 25 mm, and the overall dimensions are 75 mm wide × 130 mm high × 60 mm deep. The enclosure is IP20 (finger-safe) and IK07 (impact-resistant to 2 J). No earth-leakage or neutral protection module is integrated — this is a straight 3-pole breaker for 3-phase 3-wire systems.","metaTitle":"Schneider Electric EZC100F3025 EasyPact EZC100F 25A 3P MCCB,","metaDescription":"Schneider Electric EZC100F3025 EasyPact EZC100F 3-pole MCCB, 25 A thermal-magnetic TM-D trip, 25 kA breaking capacity at 240 V AC. IEC 60947-2. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"25 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$45.84","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/13cf36487c8c3653746991a36390f4d4.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100F3025/circuit-breakereasypact-ezc100f-tmd-25a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100F3025/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100F3025","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100F3025 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}