{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100F3045","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100F3045","canonicalUrl":"https://aoctrl.com/schneider/EZC100F3045","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100F3045","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100F, 3-pole circuit breaker, 45 A thermal-magnetic TM-D trip unit, 25 kA Icu at 240 V AC, front connection, toggle control.","salesMarkdown":"The EZC100F3045 is a 3-pole EasyPact EZC100F moulded-case circuit breaker from Schneider Electric, rated 45 A at 40 °C (45 A at 50 °C with the TM-D thermal-magnetic trip unit). The 25 kA Icu at 220…240 V AC is the interrupting capacity that determines whether this breaker clears a fault without upstream devices needing to trip — at 380…415 V AC that figure drops to 10 kA Icu, and at 440 V AC to 7.5 kA Icu, so selectivity coordination needs to be checked at your actual system voltage. The 690 V AC rated insulation voltage (Ui) and 550 V AC maximum operational voltage (Ue) cover standard 400 V distribution panels with headroom. IP20 finger protection on the front face is fine for enclosed panels; the IK07 impact rating means the enclosure can take a light tool strike during installation without cracking the housing. Certified to EN/IEC 60947-2 and EN/IEC 60947-1, plus JIS C8201-2-2 and GB/T 14048.2 for Japanese and Chinese markets. Pollution degree 3 (conductive pollution from condensation or light dust) is standard for industrial control panels. No earth-leakage or neutral protection built in; this is a straight overload and short-circuit device for 3-phase loads.","metaTitle":"Schneider Electric EZC100F3045 EasyPact EZC100F Circuit Brea","metaDescription":"Schneider Electric EZC100F3045 EasyPact EZC100F 3-pole circuit breaker, 45 A thermal-magnetic TM-D trip unit, 25 kA breaking capacity at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ccf8a9b44628be07ec93b398459088c0.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100F3045/circuit-breaker-easypact-ezc100f-tmd-45-a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100F3045/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100F3045","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100F3045 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}