{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100F3063","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100F3063","canonicalUrl":"https://aoctrl.com/schneider/EZC100F3063","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100F3063","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100F, EZC100F3063, 3-pole MCCB, 63 A thermal-magnetic trip unit, 25 kA Icu at 240 V AC, IP20.","salesMarkdown":"The Schneider Electric EZC100F3063 is a 3-pole EasyPact EZC100F moulded-case circuit breaker with a thermal-magnetic TM-D trip unit rated 63 A at 50 °C. The thermal-magnetic trip gives you an inverse-time overload curve (the thermal bimetal) plus instantaneous magnetic short-circuit protection, so it covers both sustained overloads and hard faults in one compact package. Breaking capacity is where this breaker earns its keep in a distribution panel. Drop to 380–415 V AC and it still handles 10 kA; at 440 V AC it holds 7.5 kA; at 550 V AC it manages 5 kA. On the DC side, it breaks 5 kA at 125 V DC (1-pole) and 5 kA at 250 V DC (2-pole). For a 63 A feeder in a 400 V panel with a typical transformer impedance, 10 kA is usually enough headroom — but if your upstream transformer is oversized or your fault current study shows higher, check the 25 kA 240 V number against your service-entrance rating. ## Mounting and enclosure fit This breaker mounts fixed to a backplate, not on a DIN rail. That is typical for Moulded-Case Circuit Breakers (MCCBs) in this frame size — you bolt it to the panel's mounting plate, torque the terminals to spec, and wire front-to-front. The 25 mm connection pitch spaces the phase terminals evenly, which keeps busbar and cable-lug alignment predictable. IP20 finger-safe protection means the front face is touch-safe when the cover is on; IK07 impact resistance handles the odd dropped tool during commissioning. ## Standards and approvals — what they certify It also carries GB/T 14048.2 (China) and JIS C8201-2-2 (Japan) marks, so it is accepted across major global markets without a separate re-certification. Lifecycle status is current production. No EOL notice or last-time-buy on record. This is a standard catalogue item in Schneider's EasyPact range, so it is not a niche or legacy SKU that might vanish on short notice.","metaTitle":"Schneider Electric EZC100F3063 EasyPact EZC100F, 63 A, 25 kA","metaDescription":"Schneider Electric EZC100F3063 EasyPact EZC100F MCCB, 63 A thermal-magnetic, 25 kA Icu at 240 V AC. EN/IEC 60947-2, IP20. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"75 mm","title":"EZC100F3063","Height":"130 mm","Standards":"EN/IEC 60947-2 GB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-1","description":"circuit breaker Easypact EZC100F - TMD - 63 A - 3 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"63 A at 50 °C","Breaking capacity":"25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 125 V DC 1P conforming to IEC 60947-2 5 kA Icu at 250 V DC 2P conforming to IEC 60947-2 5 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 10 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100F","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"63 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100F","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"F","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"2.5 kA at 125 V DC conforming to IEC 60947-2 2.5 kA at 250 V DC conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 3.75 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 380...415 V AC 50/60 Hz conforming to IEC 60947-2 12.5 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$45.84","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/3c750bd95525a5442e2ddfec3bd75df3.pdf","sourceUrl":"https://www.se.com/ng/en/product/EZC100F3063/circuit-breaker-easypact-ezc100f-tmd-63-a-3-poles-3d/"},"ai":{"faq":[{"question":"What is the closest alternative to the EZC100F3063 in the EasyPact family?","answer":"Within the EasyPact EZC100F frame, the closest sibling is the same breaker with a different trip rating or breaking capacity code. The F code (25 kA at 240 V) is the mid-range interrupting capacity; a G-code version offers higher Icu if your fault study demands it, while an N-code steps down for lower-cost installations where fault current is under 10 kA. All share the same footprint and terminal pitch, so swapping trip units or frame ratings requires no panel rework."},{"question":"What compliance documentation does Schneider provide for the EZC100F3063?","answer":"The breaker is certified to EN/IEC 60947-2, GB/T 14048.2, and JIS C8201-2-2. It carries a CE mark for the European market. RoHS and REACH declarations are standard from Schneider for this product family — request them with your RFQ if you need them for your compliance file."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100F3063","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100F3063 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}