{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H1016","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H1016","canonicalUrl":"https://aoctrl.com/schneider/EZC100H1016","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H1016","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, circuit breaker, EZC100H1016, 16 A, 1P, 25 kA Icu at 110-130 V AC, thermal-magnetic TM-D trip unit.","salesMarkdown":"The EZC100H1016 is a 1-pole EasyPact EZC100H circuit breaker with a thermal-magnetic TM-D trip unit rated 16 A at 50 °C. The 25 mm width per pole fits standard 25 mm pitch distribution boards — a single-pole unit occupies one module position. The breaking capacity code H delivers 25 kA Icu at 110-130 V AC and 50 kA Icu at 220-240 V AC, which covers most commercial lighting and small-load branch circuits; at 380-400 V AC it drops to 5 kA, so verify the available fault current at the installation point if feeding a 400 V line. The 10 kA Icu at 125 V DC makes it usable in DC distribution panels up to that voltage, but only for single-pole switching. ## Deployment context IP20 finger-safe terminals allow installation in enclosed panels without additional shrouding. The toggle control provides positive contact indication — the handle position shows the contact state even if the mechanism is damaged. Mechanical durability is 13,000 cycles, which is standard for a distribution-grade breaker; not rated for frequent switching duty.","metaTitle":"Schneider Electric EZC100H1016 EasyPact EZC100H, 16 A, 1P, 2","metaDescription":"Schneider Electric EZC100H1016 EasyPact EZC100H circuit breaker, 16 A thermal-magnetic, 1-pole, 25 kA breaking capacity at 110-130 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"25 mm","Height":"130 mm","Voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/0bc711f145ffb16a3e972be7ebe9abeb.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H1016/circuit-breakereasypact-ezc100h-tmd-16a-1-pole-1d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H1016/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H1016","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H1016 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}