{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H1020","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H1020","canonicalUrl":"https://aoctrl.com/schneider/EZC100H1020","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H1020","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H1020, 1-pole thermal-magnetic circuit breaker, 20 A rated current, 25 kA Icu at 240 V AC, toggle control, front connection.","salesMarkdown":"The Schneider Electric EZC100H1020 is a 1-pole EasyPact EZC100H thermal-magnetic circuit breaker rated 20 A at 40 °C, with a TM-D trip unit providing both short-circuit and overload protection. The 20 A rating at 50 °C tells you the breaker can carry its full load in a warmer panel — useful if the enclosure runs hot from adjacent devices. Breaking capacity is 25 kA Icu at 220...240 V AC, which means it can safely interrupt a fault current up to 25,000 A at typical North American line voltage without welding its contacts or rupturing. The part carries a Category A utilization rating, meaning it is not intended for current-limiting duty under short-circuit conditions; it simply clears the fault within its rated Icu. The single pole protects one phase, and there is no neutral or earth-leakage protection built in. Mechanical durability is rated at 13,000 cycles — fine for distribution panels where the breaker is operated infrequently, but not a motor-starting duty cycle. ## Deployment context This breaker mounts fixed to a backplate with front-side connections — typical for panelboard or distribution board integration. The 25 mm width and 60 mm depth fit standard modular spacing; the 25 mm connection pitch aligns with common busbar systems.","metaTitle":"Schneider Electric EZC100H1020 EasyPact EZC100H Circuit Brea","metaDescription":"Schneider Electric EZC100H1020 EasyPact EZC100H circuit breaker, 20 A thermal-magnetic, 1-pole, 25 kA Icu at 240 V AC. Sourced to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"25 mm","title":"EZC100H1020","Height":"130 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-1 JIS C8201-2-2 GB/T 14048.2","description":"circuit breaker Easypact EZC100H - TMD - 20 A - 1 pole 1d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"20 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"1P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"20 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"1t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$35.67","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/bffa5f324313e3ee7d6f7404d2f8ad7c.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H1020/circuit-breaker-easypact-ezc100h-tmd-20-a-1-pole-1d/"},"ai":{"faq":[{"question":"What is the breaking capacity of EZC100H1020 at 240 V AC?","answer":"The EZC100H1020 has a breaking capacity of 25 kA Icu at 220...240 V AC 50/60 Hz per IEC 60947-2."},{"question":"Where can I buy EZC100H1020 and how is it quoted?","answer":"The EZC100H1020 is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."},{"question":"What standards does the EZC100H1020 comply with?","answer":"The EZC100H1020 complies with EN/IEC 60947-2, EN/IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H1020","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H1020 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}