{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H1032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H1032","canonicalUrl":"https://aoctrl.com/schneider/EZC100H1032","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H1032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H1032, 1-pole thermal-magnetic circuit breaker, 32 A rated current, 25 kA breaking capacity at 240 V AC, fixed mount.","salesMarkdown":"The Schneider Electric EZC100H1032 is a 1-pole EasyPact EZC100H thermal-magnetic circuit breaker rated 32 A at 50 °C (32 A at 40 °C per the In rating). It carries a 25 kA Icu breaking capacity at 220–240 V AC 50/60 Hz per IEC 60947-2, stepping down to 5 kA at 380–400 V AC and 10 kA at 125 V DC 1P. Category A utilization (no intentional short-time delay) means it trips instantaneously on fault — suited for distribution feeder duty, not selective coordination downstream of a larger breaker. Fixed mounting on a backplate, 25 mm width per pole, 60 mm depth, 130 mm height. Front connection both top and bottom. IP20 finger-safe terminals, IK07 impact resistance. Pollution degree 3 environment — install in a panel that keeps conductive dust and condensation off live parts.","metaTitle":"Schneider Electric EZC100H1032 EasyPact EZC100H Circuit Brea","metaDescription":"Schneider Electric EZC100H1032 EasyPact EZC100H circuit breaker. 32 A thermal-magnetic trip, 1-pole, 25 kA breaking capacity at 240 V AC. Active production, sourced to order. Quote","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"25 mm","Height":"130 mm","Voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/5eab2f35dbf67937c2a5f24c3fcda903.pdf","sourceUrl":"https://www.se.com/ph/en/product/EZC100H1032/circuit-breaker-easypact-ezc100h-tmd-32-a-1-pole-1d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H1032/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H1032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H1032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}