{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H1050","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H1050","canonicalUrl":"https://aoctrl.com/schneider/EZC100H1050","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H1050","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, circuit breaker, 1P, 50 A, TM-D trip unit, 25 kA Icu at 240 V AC, 10 kA at 125 V DC.","salesMarkdown":"The Schneider Electric EZC100H1050 is a 1-pole EasyPact EZC100H moulded-case circuit breaker rated 50 A at 40 °C, with a thermal-magnetic TM-D trip unit for overload and short-circuit protection. Breaking capacity varies by voltage: 50 kA Icu at 110–130 V AC, 25 kA at 220–240 V AC, 5 kA at 380 V AC and 400–415 V AC, and 10 kA at 125 V DC. The H breaking capacity code indicates the higher interrupting rating within the EZC100 frame. Dimensions: 130 mm high, 25 mm wide, 60 mm deep. IP20 finger-safe terminals; IK07 impact resistance per IEC 62262 for enclosures subject to light mechanical stress. Toggle control with positive contact indication — the handle position directly reflects the contact state, no ambiguity for the panel builder or maintenance technician. Mechanical durability is rated at 13,000 cycles. Standards compliance includes GB/T 14048.2, EN/IEC 60947-1, JIS C8201-2-2, and EN/IEC 60947-2.","metaTitle":"Schneider Electric EZC100H1050 EasyPact MCCB, 50 A, 1P, 25 k","metaDescription":"Schneider Electric EZC100H1050 EasyPact EZC100H circuit breaker, 50 A rated current, 1-pole, 25 kA breaking capacity at 240 V AC. TM-D trip unit. Active production. Available to or","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"25 mm","title":"EZC100H1050","Height":"130 mm","Standards":"GB/T 14048.2 EN/IEC 60947-1 JIS C8201-2-2 EN/IEC 60947-2","description":"circuit breaker Easypact EZC100H - TMD - 50 A - 1 pole 1d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"50 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"1P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"50 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"1t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$47.02","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b9aa82343d742635e78eba8ebf5a8330.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H1050/circuit-breaker-easypact-ezc100h-tmd-50-a-1-pole-1d/"},"ai":{"faq":[{"question":"What is the breaking capacity of EZC100H1050?","answer":"Breaking capacity is 25 kA Icu at 220–240 V AC, 50 kA at 110–130 V AC, 5 kA at 380 V AC and 400–415 V AC, and 10 kA at 125 V DC, all per IEC 60947-2."},{"question":"What is the trip unit type on EZC100H1050?","answer":"It uses a thermal-magnetic TM-D trip unit rated 50 A at 50 °C, providing overload and short-circuit protection."},{"question":"Where can I buy EZC100H1050?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution channels. Availability and current pricing are confirmed at quote time."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H1050","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H1050 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}