{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H1060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H1060","canonicalUrl":"https://aoctrl.com/schneider/EZC100H1060","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H1060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H1060, 1-pole thermal-magnetic MCCB, 60 A rated current, 25 kA breaking capacity at 240 V AC, IEC 60947-2.","salesMarkdown":"The Schneider Electric EasyPact EZC100H1060 is a 1-pole thermal-magnetic molded-case circuit breaker rated 60 A, built to IEC 60947-2 for distribution duty. It sits in the EasyPact range, which is Schneider's value line for commercial and light industrial panels where you need a reliable MCCB without the premium of a Compact NSX. The TM-D trip unit gives you fixed thermal and magnetic protection — set it and forget it, no adjustment dials. At 60 A and 1 pole, this is a single-phase feeder or branch breaker. The 25 kA breaking capacity at 220–240 V AC covers most North American commercial panel fault levels; the 5 kA at 400–415 V AC is enough for European 400 V three-phase systems where you'd use three of these (one per phase) on a sub-distribution board. The 50 kA at 110–130 V AC is overkill for most jobs but means it handles high-fault utility drops without cascading. The Icu (ultimate breaking capacity) varies by voltage because arc extinction gets harder as voltage rises. At 240 V AC you get 25 kA — that's the typical short-circuit rating for a 225 A panelboard feeder. At 415 V AC the same breaker drops to 5 kA, which is still adequate for most European distribution boards where the transformer impedance limits fault current below that. The 10 kA at 125 V DC is useful for battery-bank or UPS output circuits. If you need selectivity (keeping the upstream breaker closed while the downstream clears a fault), you step up to a Category B MCCB like the Compact NSX. For a simple radial feed, Category A is fine and saves panel space. The EZC100H1060 is in active current production. No end-of-life notice has been issued for the EasyPact EZC100H range as of the latest data. Fixed mounting on a backplate, 25 mm width per pole. Front connection top and bottom — standard for panelboard plug-on or bus-bar stabs. IP20 finger-safe terminals, IK07 impact rating. ## Temperature derating — the real-world gotcha If your panel sits in a hot machine room or near a furnace, you don't need to derate this breaker until you exceed 50 °C. Below -25 °C the thermal trip may be sluggish, but that's rare in indoor distribution. Compliant with IEC 60947-2 (the main MCCB standard globally), JIS C8201-2-2 (Japanese industrial standard), and GB/T 14048.2 (Chinese GB standard). Rated insulation voltage 690 V AC, so it's fine on 400/480 V systems with margin. No earth-leakage protection built in; if you need RCD functionality, add an external Vigi module or use the EZC100H with earth-leakage option.","metaTitle":"Schneider EasyPact EZC100H1060 60A 1P MCCB, 25kA at 240V","metaDescription":"Schneider Electric EasyPact EZC100H1060 60A thermal-magnetic MCCB, 1-pole, 25kA breaking capacity at 240V AC. Active production, sourced to order. Quoted on request.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"25 mm","title":"EZC100H1060","Height":"130 mm","Standards":"JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2 EN/IEC 60947-1","description":"circuit breaker Easypact EZC100H - TMD - 60 A - 1 pole 1d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"60 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"1P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"60 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"1t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$47.02","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1f38e49301691e5eb5bbac9cc9289304.pdf","sourceUrl":"https://www.se.com/ph/en/product/EZC100H1060/circuit-breaker-easypact-ezc100h-tmd-60-a-1-pole-1d/"},"ai":{"faq":[{"question":"Who supplies EZC100H1060 and how is it quoted for volume purchases?","answer":"This part is sourced through independent distribution channels and quoted to order against an RFQ. Availability and current pricing are confirmed at quote time."},{"question":"What is EZC100H1060's breaking capacity at 240 V AC?","answer":"25 kA Icu at 220–240 V AC, 50/60 Hz, per IEC 60947-2."},{"question":"What is the operating temperature range for EZC100H1060?","answer":"-25 °C to 70 °C for operation, -35 °C to 85 °C for storage."},{"question":"What compliance standards does EZC100H1060 meet?","answer":"IEC 60947-2, JIS C8201-2-2, GB/T 14048.2, and IEC 60947-1. Suitable for isolation per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H1060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H1060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}