{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H1063","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H1063","canonicalUrl":"https://aoctrl.com/schneider/EZC100H1063","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H1063","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H1063, 1-pole thermal-magnetic circuit breaker, 63 A rated current, 5 kA breaking capacity at 400 V AC, IP20.","salesMarkdown":"The Schneider Electric EZC100H1063 is a 1-pole EasyPact EZC100H circuit breaker with a thermal-magnetic trip unit (TM-D) rated 63 A at 50 °C. It carries a 5 kA Icu breaking capacity at 380–400 V AC 50/60 Hz per IEC 60947-2, which is the figure that governs its use in standard 400 V distribution panels — at 240 V AC that same rating climbs to 25 kA, and at 125 V DC it holds 10 kA. If your panel runs hotter, you derate; if it runs at 40 °C, the same breaker is rated 63 A — so the 50 °C figure is the conservative one. Below 240 V AC the same breaker handles 25 kA, so it's not a weak unit — it's sized for the 400 V distribution tier. The TM-D trip unit is the standard fixed-trip version — no interchangeable rating coils, no electronic adjustment. For a fixed-load branch circuit where you don't need field-adjustable trip settings, this keeps the BOM simple. The breaker is certified for isolation per IEC 60947-2, meaning you can use it as a disconnecting means with a visible gap when toggled off — the positive contact indication confirms the contact position visually. This is a fixed-mount backplate-mounted breaker with front-front connections — both line and load terminate on the front face. The 25 mm width and 25 mm connection pitch are standard for a 1-pole miniature-frame breaker; it occupies one 25 mm module on a DIN rail or backplate. IP20 means finger-safe from the front but not sealed against dust ingress — fine for a closed panel, not for washdown areas. Mechanical durability is 13,000 cycles — that's the number of on-off operations before the mechanism wears out, not the electrical endurance under load. For a distribution breaker that cycles a few times a year, that's effectively a lifetime.","metaTitle":"Schneider Electric EZC100H1063 EasyPact EZC100H Circuit Brea","metaDescription":"Schneider Electric EZC100H1063 EasyPact EZC100H circuit breaker. 63 A thermal-magnetic trip, 5 kA breaking capacity at 400 V AC. IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"25 mm","Height":"130 mm","Voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$47.02","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/1f7f7f082bffa38a43753cbf55d8de7e.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H1063/circuit-breaker-easypact-ezc100h-tmd-63-a-1-pole-1d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H1063/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H1063","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H1063 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}