{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H1100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H1100","canonicalUrl":"https://aoctrl.com/schneider/EZC100H1100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H1100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, 1-pole 100 A thermal-magnetic MCCB, TM-D trip unit, 25 kA Icu at 240 V AC, 10 kA Icu at 125 V DC, fixed mount, toggle control.","salesMarkdown":"It's 25 mm wide — one pole wide — so it slots into a backplate-mounted assembly without eating up rail space. The 25 kA Icu at 240 V AC means it'll clear a substantial fault on a 240 V distribution bus without upstream coordination headaches; at 415 V AC it's 5 kA Icu, so watch the system SCCR if you're using it on a 400 V line. It's a Category A breaker — no intentional short-time delay, so it's meant for instant trip on fault, not selective coordination with downstream devices. The breaking capacity code 'H' tells you this is the high-interrupting version of the EZC100 frame. At 125 V DC it's 10 kA Icu, which covers battery-bank and UPS output breakers in telecom/DC plant applications. The IP20 finger-safe terminals and IK07 impact resistance handle the usual enclosure-installation abuse. Mechanical durability of 13,000 cycles — that's the expected life of the mechanism under no-load switching. For a distribution breaker that cycles a few times a year in normal service, that's effectively a lifetime. If you're switching it daily as a disconnect, you'll want to check the electrical endurance curve (not in this spec set) for the actual load current. ## Mounting & connections Fixed mount on a backplate — no DIN rail adapter on this one. The 25 mm pole pitch matches standard panelboard busbar spacing. Front connections both top and bottom, so busbar runs and load cables land on the same face. Connection pitch is 25 mm, which aligns with standard distribution lug kits. Toggle control with positive contact indication — you can see the contact position through the front window, not just the handle position. That matters for lockout/tagout verification.","metaTitle":"Schneider EasyPact EZC100H1100 1P 100A MCCB, 25kA at 240V","metaDescription":"Schneider Electric EasyPact EZC100H1100 1-pole 100A thermal-magnetic MCCB. 25kA breaking at 240V AC, 10kA at 125V DC. Current lifecycle stage, sourced to order. IEC 60947-2.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"25 mm","title":"EZC100H1100","Height":"130 mm","Standards":"GB/T 14048.2 EN/IEC 60947-2 EN/IEC 60947-1 JIS C8201-2-2","description":"circuit breaker,EasyPact EZC100H,TMD, 100A,1 pole 1d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"100 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 25 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"1P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"100 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"1t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"125 V DC conforming to IEC 60947-2 415 V AC 50/60 Hz conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 12.5 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/2c2afe4f2f223594f6e2b77185d13cd2.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H1100/circuit-breakereasypact-ezc100h-tmd-100a-1-pole-1d/"},"ai":{"faq":[{"question":"Where can I buy the EZC100H1100 and what is the lead time?","answer":"Sourced and quoted to order against an RFQ through our independent distribution network. Availability and current pricing confirmed at quote time."},{"question":"What is the breaking capacity of the EZC100H1100 at 240 V?","answer":"25 kA Icu at 220...240 V AC 50/60 Hz per IEC 60947-2. At 415 V AC it's 5 kA Icu."},{"question":"What standards does the EZC100H1100 comply with?","answer":"It complies with GB/T 14048.2, EN/IEC 60947-2, EN/IEC 60947-1, and JIS C8201-2-2. Suitable for isolation per IEC 60947-2."},{"question":"What is the width of the EZC100H1100?","answer":"25 mm — single-pole width for a 1-pole MCCB."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H1100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H1100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}