{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H2016","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H2016","canonicalUrl":"https://aoctrl.com/schneider/EZC100H2016","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H2016","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H2016, 2-pole circuit breaker, 16 A rated current, TM-D thermal-magnetic trip unit, 10 kA Icu at 125 V DC.","salesMarkdown":"Breaking capacity is the key selection figure here. At 125 V DC single-pole it clears 10 kA Icu per IEC 60947-2; at 250 V DC 2-pole it also clears 10 kA. On AC, the 380…400 V 50/60 Hz rating is 30 kA Icu, and at 220…240 V it reaches 50 kA Icu. The unit is front-connected top and bottom, mounts fixed to a backplate, and uses a toggle for manual control. Positive contact indication gives a visual confirmation of the contact position independent of the toggle mechanism — useful during panel commissioning when you need to verify isolation without assuming the handle position. Dimensions are 130 mm high, 50 mm wide, 60 mm deep. The 2-pole configuration protects both poles (2t) with no neutral protection. If your circuit requires a switched neutral or a 4-pole break, this is not the variant. For a straightforward 2-wire distribution feed — single-phase or DC — it fits without extra wiring complexity. The breaker is certified to JIS C8201-2-2, EN/IEC 60947-2, GB/T 14048.2, and EN/IEC 60947-1. Rated insulation voltage is 690 V AC, operational voltage is 550 V AC or 250 V DC — the DC rating covers common 125 V and 250 V battery or rectifier circuits. The 16 A rating at 40 °C is the standard reference; at 50 °C the trip unit still carries 16 A, so no derating is needed up to that temperature for the trip unit itself — though the overall breaker rating at 40 °C is the one to use for NEC or IEC cable sizing.","metaTitle":"Schneider Electric EZC100H2016 EasyPact EZC100H Circuit Brea","metaDescription":"Schneider Electric EZC100H2016 EasyPact EZC100H circuit breaker, 16 A rated current, 2 poles, TM-D trip unit, 10 kA Icu at 125 V DC. Quoted to order against RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"50 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/39f2e52bc9a5e9dbb7ef74be6188d00e.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H2016/circuit-breakereasypact-ezc100h-tmd-16a-2-poles-2d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H2016/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H2016","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H2016 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}