{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H2020","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H2020","canonicalUrl":"https://aoctrl.com/schneider/EZC100H2020","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H2020","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H2020, 2-pole MCCB, 20 A rated current, TM-D thermal-magnetic trip unit, breaking capacity 10-100 kA Icu per IEC 60947-2.","salesMarkdown":"The EZC100H2020: Breaking capacity varies by voltage: 100 kA Icu at 110-130 V AC, 50 kA at 220-240 V AC, 30 kA at 380-415 V AC, 20 kA at 440 V AC, 10 kA at 550 V AC, and 10 kA at 125 V DC (1P) or 250 V DC (2P). That covers most industrial panel secondary-side fault levels without cascading upstream. The TM-D trip is thermal-magnetic, providing overload and short-circuit protection. Rated 20 A at 50 °C ambient, with a 20 A In at 40 °C. Fixed backplate mount, 130 mm high, 50 mm wide, 60 mm deep. Connection pitch 25 mm. IP20 finger-safe enclosure; IK07 impact rating handles incidental tool contact in the cabinet. Toggle control with positive contact indication — the handle position reflects the actual contact state, not just the mechanism.","metaTitle":"Schneider Electric EZC100H2020 EasyPact EZC100H 20A 2P MCCB,","metaDescription":"Schneider Electric EZC100H2020 EasyPact EZC100H 20A 2-pole MCCB. Breaking capacity 10-100kA Icu per IEC 60947-2. TM-D thermal-magnetic trip. Current production. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"50 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$52.89","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d0a0c36a2720ad3c95a8f7363f13c60e.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H2020/circuit-breaker-easypact-ezc100h-tmd-20-a-2-poles-2d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H2020/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H2020","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H2020 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}