{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H2025","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H2025","canonicalUrl":"https://aoctrl.com/schneider/EZC100H2025","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H2025","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H2025, 2-pole thermal-magnetic circuit breaker, 25 A rated current, breaking capacity 10-100 kA AC/DC, IEC 60947-2.","salesMarkdown":"The EZC100H2025 is a 2-pole thermal-magnetic circuit breaker from the Schneider Electric EasyPact EZC100H range, rated 25 A at 40 °C (25 A at 50 °C with the TM-D trip unit). The 25 A continuous rating sets the maximum load current before the thermal element begins to trip — sized for a 25 A feeder or branch circuit on a distribution panel. The magnetic (short-circuit) element reacts to instantaneous overcurrents, with breaking capacity (Icu) ranging from 10 kA at 125 V DC / 550 V AC up to 100 kA at 110–130 V AC, all per IEC 60947-2. At 400–415 V AC the Icu is 30 kA; at 440 V AC it's 20 kA. For DC circuits, 10 kA at 125 V DC (1-pole) or 250 V DC (2-pole). ## Deployment context Mounts fixed to a backplate (not DIN rail) with front-front connections — both line and load terminate on the front face, which simplifies busbar and cable routing in a distribution board. The IP20 finger-safe enclosure suits dry indoor panels; the IK07 impact rating means it withstands accidental tool drops during panel assembly. Certified to GB/T 14048.2, EN/IEC 60947-1, JIS C8201-2-2, and EN/IEC 60947-2 — covering China, Europe, Japan, and the international IEC standard. No earth-leakage protection built in; if ground-fault protection is needed, an external RCD or earth-leakage module must be added.","metaTitle":"Schneider Electric EZC100H2025 EasyPact EZC100H, 25 A, 2-Pol","metaDescription":"Schneider Electric EZC100H2025 EasyPact EZC100H circuit breaker, 25 A thermal-magnetic, 2-pole, breaking capacity 10-100 kA, IEC/GB/JIS compliant, current lifecycle. Sourced to ord","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"50 mm","title":"EZC100H2025","Height":"130 mm","Standards":"GB/T 14048.2 EN/IEC 60947-1 JIS C8201-2-2 EN/IEC 60947-2","description":"circuit breaker Easypact EZC100H - TMD - 25 A - 2 poles 2d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"25 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"2P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"25 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"2t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$52.89","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/ee69d50be5f190add3c8196060c76bf5.pdf","sourceUrl":"https://www.se.com/ng/en/product/EZC100H2025/circuit-breaker-easypact-ezc100h-tmd-25-a-2-poles-2d/"},"ai":{"faq":[{"question":"Where can I buy EZC100H2025 and how do I get a price?","answer":"The EZC100H2025 is sourced to order through independent distribution. Submit an RFQ for current pricing and availability — confirmed at quote time."},{"question":"What is the breaking capacity of EZC100H2025 at 400 V AC?","answer":"At 400–415 V AC 50/60 Hz, the breaking capacity (Icu) is 30 kA per IEC 60947-2."},{"question":"What compliance documentation does Schneider provide for EZC100H2025?","answer":"The breaker is certified to GB/T 14048.2, EN/IEC 60947-1, JIS C8201-2-2, and EN/IEC 60947-2. It is suitable for isolation per IEC 60947-2. No earth-leakage protection is included."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H2025","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H2025 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}