{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H2032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H2032","canonicalUrl":"https://aoctrl.com/schneider/EZC100H2032","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H2032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H2032, 2-pole circuit breaker, 32 A rated current, TM-D thermal-magnetic trip unit, 10 kA Icu at 125 V DC.","salesMarkdown":"The EZC100H2032 is a 2-pole EasyPact EZC100H circuit breaker from Schneider Electric, rated 32 A at 40 °C (trip unit set at 32 A at 50 °C). The TM-D thermal-magnetic trip unit handles overload and short-circuit protection — the thermal element responds to sustained overcurrent, the magnetic element trips instantaneously on high fault currents. Breaking capacity varies by voltage: 10 kA Icu at 125 V DC (1-pole), 10 kA at 250 V DC (2-pole), and 30 kA Icu at 380–400 V AC. ## Deployment context IP20 finger-safe terminals; IK07 impact rating means it survives accidental tool drops. Front-connect terminals (both line and load) simplify bus-bar or cable routing in a distribution board.","metaTitle":"Schneider Electric EZC100H2032 EasyPact EZC100H, 32 A, 2-Pol","metaDescription":"Schneider Electric EZC100H2032 EasyPact EZC100H circuit breaker, 32 A rated current, 2 poles, TM-D thermal-magnetic trip unit. Breaking capacity 10 kA Icu at 125 V DC. Current life","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"50 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$52.89","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/da1a2a3f2f4305854d9f9686fabf171e.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H2032/circuit-breakereasypact-ezc100h-tmd-32a-2-poles-2d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H2032/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H2032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H2032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}