{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H2040","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H2040","canonicalUrl":"https://aoctrl.com/schneider/EZC100H2040","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H2040","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H2040, 2-pole MCCB, 40 A rated current, TM-D thermal-magnetic trip, 10–100 kA breaking capacity, IP20.","salesMarkdown":"The Schneider Electric EZC100H2040 is a 2-pole EasyPact EZC100H moulded-case circuit breaker rated 40 A at 40 °C, with a TM-D thermal-magnetic trip unit. The 40 A trip rating at 50 °C means the breaker holds full load without nuisance tripping in a warm panel — the TM-D curve handles motor inrush and distribution loads. Breaking capacity varies by voltage: 100 kA Icu at 110–130 V AC, 50 kA at 220–240 V AC, 30 kA at 380–415 V AC, 20 kA at 440 V AC, and 10 kA at 550 V AC 50/60 Hz, all per IEC 60947-2. On DC, it delivers 10 kA Icu at 125 V DC (1-pole) and 250 V DC (2-pole). The H breaking-capacity code means this is the high-interrupting version of the EZC100 frame — sized for distribution panels where fault currents can hit 100 kA on low-voltage AC. IP20 finger-safe terminals and IK07 impact resistance cover handling during installation. ## Deployment context Fixed backplate mounting with front-facing connections — upside and downside both front-connect, so it panels into a distribution board or enclosure with a 25 mm connection pitch. The 2-pole format (2t protected poles, no neutral protection) suits single-phase or DC branch circuits where only the line and switched neutral need protection. Mechanical durability of 13,000 cycles fits distribution duty (not frequent switching like a contactor).","metaTitle":"Schneider EasyPact EZC100H2040 40A 2P MCCB, 10-100kA IC","metaDescription":"Schneider Electric EasyPact EZC100H2040 40A 2-pole MCCB. TM-D trip unit, 10-100 kA breaking capacity, IP20, IEC 60947-2. Sourced to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"50 mm","title":"EZC100H2040","Height":"130 mm","Standards":"GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2","description":"circuit breaker Easypact EZC100H - TMD - 40 A - 2 poles 2d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"40 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"2P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"40 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"2t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$52.89","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/193dce69753a483840adc718d285171f.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H2040/circuit-breaker-easypact-ezc100h-tmd-40-a-2-poles-2d/"},"ai":{"faq":[{"question":"What breaking capacity does the EZC100H2040 have at 240 V AC?","answer":"50 kA Icu at 220–240 V AC 50/60 Hz per IEC 60947-2. At 400–415 V AC it drops to 30 kA Icu, and at 440 V AC to 20 kA Icu."},{"question":"What standards does the EZC100H2040 comply with?","answer":"It complies with GB/T 14048.2, EN/IEC 60947-1, EN/IEC 60947-2, and JIS C8201-2-2. It is also suitable for isolation per IEC 60947-2."},{"question":"Where can I buy the EZC100H2040?","answer":"Sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures or lead-time numbers are published here."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H2040","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H2040 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}