{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H2045","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H2045","canonicalUrl":"https://aoctrl.com/schneider/EZC100H2045","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H2045","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, 45 A, 2-pole, thermal-magnetic circuit breaker, TM-D trip unit, 10-100 kA breaking capacity, IEC 60947-2.","salesMarkdown":"The EZC100H2045 is a 2-pole EasyPact EZC100H thermal-magnetic circuit breaker rated 45 A at 40 °C (trip unit TM-D). The 45 A rating at 50 °C means the breaker is calibrated for continuous load at elevated panel temperatures — no derating guesswork for a warm enclosure. Breaking capacity spans 10 kA Icu at 125 V DC (1P) up to 100 kA Icu at 110–130 V AC, with 30 kA at 380–400 V AC and 20 kA at 440 V AC. The 2-pole configuration with front-front connections makes it a direct fit for single-phase or two-wire DC branch circuits in panelboards. ## Deployment context Fixed backplate mounting with a 25 mm connection pitch — this breaker is designed for distribution panels where the busbar spacing matches standard 25 mm centers. IP20 finger-safe terminals and IK07 impact resistance suit it for enclosed panel installation where accidental contact is a concern.","metaTitle":"Schneider Electric EZC100H2045 EasyPact EZC100H, 45 A, 2P, 1","metaDescription":"Schneider Electric EZC100H2045 EasyPact EZC100H circuit breaker, 45 A, 2-pole, thermal-magnetic TM-D trip, 10-100 kA breaking capacity, IEC 60947-2. Available to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"50 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/19f30018a8562ab9ca8cb7b44574cbb9.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H2045/circuit-breaker-easypact-ezc100h-tmd-45-a-2-poles-2d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H2045/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H2045","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H2045 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}