{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H2050","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H2050","canonicalUrl":"https://aoctrl.com/schneider/EZC100H2050","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H2050","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H2050, thermal-magnetic circuit breaker, 50 A, 2 poles, 10–100 kA breaking capacity, IP20, IK07.","salesMarkdown":"The EZC100H2050 is a 2-pole thermal-magnetic circuit breaker from the Schneider Electric EasyPact EZC100H series, rated 50 A at 40 °C. The TM-D trip unit provides short-circuit and overload protection. The H breaking capacity code means it delivers 10 kA Icu at 550 V AC, 30 kA at 400–415 V AC, and 50 kA at 220–240 V AC — so it can interrupt fault currents up to those levels without upstream coordination issues. For DC circuits, it breaks 10 kA at 125 V DC (1P) or 250 V DC (2P). The 690 V AC rated insulation voltage and Category A utilization confirm it is designed for distribution panelboard duty, not motor-starting cycles. IP20 finger-safe terminals and IK07 impact resistance suit it for backplate mounting in a locked panel. ## Deployment context Mounts fixed to a backplate with front-front connections at a 25 mm pitch. The toggle control provides positive contact indication — the handle position shows whether the contacts are open or closed, which aids troubleshooting during commissioning. Designed to EN/IEC 60947-1 and EN/IEC 60947-2, plus JIS C8201-2-2 and GB/T 14048.2. No earth-leakage protection is integrated; the neutral pole is unprotected. The 13,000-cycle mechanical durability is typical for distribution breakers — not a high-cycle motor-switching device.","metaTitle":"Schneider Electric EZC100H2050 EasyPact EZC100H Circuit Brea","metaDescription":"Schneider Electric EZC100H2050 EasyPact EZC100H thermal-magnetic circuit breaker, 50 A rated current, 2 poles, 10-100 kA breaking capacity. Current lifecycle stage. Sourced to orde","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"50 mm","title":"EZC100H2050","Height":"130 mm","Standards":"JIS C8201-2-2 EN/IEC 60947-1 GB/T 14048.2 EN/IEC 60947-2","description":"circuit breaker Easypact EZC100H - TMD - 50 A - 2 poles 2d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"50 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"2P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"50 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"2t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/b6b6cba67763a88abcfcea9318e2e493.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H2050/circuit-breaker-easypact-ezc100h-tmd-50-a-2-poles-2d/"},"ai":{"faq":[{"question":"What is the breaking capacity of EZC100H2050 at 400 V AC?","answer":"30 kA Icu at 400–415 V AC 50/60 Hz per IEC 60947-2. At 440 V AC it drops to 20 kA, and at 550 V AC to 10 kA."},{"question":"Where can I buy EZC100H2050 and how is it quoted?","answer":"This part is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock figures are published here."},{"question":"What compliance documentation does Schneider provide for EZC100H2050?","answer":"The breaker is designed to EN/IEC 60947-1 and EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It carries IP20 and IK07 ratings. For RoHS/REACH declarations, refer to the manufacturer's product environmental profile."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H2050","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H2050 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}