{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H2060","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H2060","canonicalUrl":"https://aoctrl.com/schneider/EZC100H2060","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H2060","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H2060, 2-pole molded case circuit breaker, 60 A thermal-magnetic TM-D trip unit, 10–100 kA breaking capacity, IP20, backplate mount.","salesMarkdown":"It's a distribution-grade breaker (Category A per IEC 60947-2) for fixed backplate mounting in panels. The 10 kA Icu at 550 V AC and 100 kA Icu at 110–130 V AC tell you where it can sit in the fault-current hierarchy: upstream on a 100 kA-capable transformer secondary, or downstream on a 10 kA branch. The 20 kA at 440 V AC and 30 kA at 400–415 V AC cover standard 400 V three-phase distribution panels. The 10 kA at 250 V DC 2P matters for DC bus or battery-string protection. ## Integration notes Mounts fixed to a backplate — no DIN rail adapter. The 25 mm connection pitch and front-facing terminals (upside and downside) suit panel layouts where busbars or cable lugs land from the front. The toggle handle gives positive contact indication (open/closed visible). The IP20 finger-safe enclosure is standard for enclosed panels; the IK07 impact rating handles accidental tool drops during commissioning. The 13000-cycle mechanical durability is typical for distribution breakers — fine for infrequent switching, not for daily motor-start duty. Certified to EN/IEC 60947-2 and EN/IEC 60947-1, plus JIS C8201-2-2 and GB/T 14048.2.","metaTitle":"Schneider Electric EZC100H2060 EasyPact EZC100H 60 A, 2-Pole","metaDescription":"Schneider Electric EZC100H2060 EasyPact EZC100H 2-pole circuit breaker, 60 A thermal-magnetic TM-D trip, 10-100 kA breaking capacity, IP20, current lifecycle. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"50 mm","title":"EZC100H2060","Height":"130 mm","Standards":"JIS C8201-2-2 GB/T 14048.2 EN/IEC 60947-2 EN/IEC 60947-1","description":"circuit breaker,EasyPact EZC100H,TMD, 60A,2 poles 2d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Range of product":"EasyPact","Trip unit rating":"60 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"2P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"60 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to IEC 62262","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"2t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"15 kA at 380 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 50 kA at 110/130 V AC 50/60 Hz conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 400/415 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220/230/240 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$52.89","stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/38f4c25cea2e697577fbc0a0873aadd9.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H2060/circuit-breakereasypact-ezc100h-tmd-60a-2-poles-2d/"},"ai":{"faq":[{"question":"How do I get current pricing and availability for EZC100H2060?","answer":"Pricing and availability are confirmed at quote time. Submit an RFQ through this listing; we source it through independent distribution channels and will respond with current lead time and price."},{"question":"What is the breaking capacity of EZC100H2060 at 400 V AC?","answer":"The EZC100H2060 delivers 30 kA Icu at 400–415 V AC 50/60 Hz per IEC 60947-2, and 20 kA Icu at 440 V AC. At 220–240 V AC it achieves 50 kA Icu."},{"question":"What compliance documentation does this brand provide for EZC100H2060?","answer":"The breaker is certified to EN/IEC 60947-2, EN/IEC 60947-1, JIS C8201-2-2, and GB/T 14048.2. It carries IP20 and IK07 protection ratings and is suitable for isolation per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H2060","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H2060 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-08-11T15:51:03.652Z","lastPublished":"2026-08-11T15:51:03.652Z","indexable":true}}