{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H3016","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H3016","canonicalUrl":"https://aoctrl.com/schneider/EZC100H3016","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H3016","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H3016, 3-pole molded-case circuit breaker, 16 A thermal-magnetic TM-D trip unit, breaking capacity code H, fixed mount, toggle control.","salesMarkdown":"The EZC100H3016 is a 3-pole molded-case circuit breaker from the EasyPact EZC100H range, rated 16 A at 40 °C (trip unit TM-D, thermal-magnetic). The 'H' breaking capacity code delivers 100 kA Icu at 110–130 V AC, 50 kA at 220–240 V AC, 30 kA at 380–415 V AC, 20 kA at 440 V AC, and 10 kA at 550 V AC — all per IEC 60947-2. On the DC side it holds 10 kA at 125 V DC (1P) or 250 V DC (2P). No earth-leakage protection built in — if you need GFCI, add an external Vigi module. Fixed backplate mount, front connections both line and load sides. Dimensions: 130 mm high, 75 mm wide, 60 mm deep — fits a standard 3-pole MCCB footprint with 25 mm connection pitch. IP20 finger-safe on the front; IK07 impact resistance means it survives a moderate tool drop during installation. Current-production part — no end-of-life notice. The EasyPact EZC100H series is Schneider's economy molded-case breaker line for distribution duty.","metaTitle":"Schneider Electric EZC100H3016 EasyPact EZC100H Circuit Brea","metaDescription":"Schneider Electric EZC100H3016 EasyPact EZC100H 3-pole circuit breaker, 16 A thermal-magnetic TM-D trip unit, breaking capacity up to 100 kA at 240 V AC. Sourced to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"75 mm","title":"EZC100H3016","Height":"130 mm","Standards":"GB/T 14048.2 EN/IEC 60947-1 EN/IEC 60947-2 JIS C8201-2-2","description":"circuit breaker,EasyPact EZC100H,TMD, 16A,3 poles 3d","Control type":"Toggle","Network type":"AC DC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"16 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"16 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fb955a0c6af02eee8eb18028ed008480.pdf","sourceUrl":"https://www.se.com/eg/en/product/EZC100H3016/circuit-breakereasypact-ezc100h-tmd-16a-3-poles-3d/"},"ai":{"faq":[{"question":"What are the key ratings of the EZC100H3016?","answer":"16 A rated current at 40 °C, thermal-magnetic TM-D trip unit, 3 poles, breaking capacity up to 100 kA Icu at 240 V AC and 30 kA at 400 V AC per IEC 60947-2. No earth-leakage protection built in."},{"question":"What compliance documentation does Schneider provide for EZC100H3016?","answer":"The breaker is certified to GB/T 14048.2, EN/IEC 60947-1, EN/IEC 60947-2, and JIS C8201-2-2. It carries IP20 protection, IK07 impact rating, and is suitable for isolation per IEC 60947-2. Specific RoHS/REACH declarations are available from Schneider's product documentation portal."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H3016","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H3016 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}