{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H3016","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H3016","canonicalUrl":"https://aoctrl.com/schneider/EZC100H3016","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H3016","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H3016, 3-pole molded-case circuit breaker, 16 A thermal-magnetic TM-D trip unit, breaking capacity code H, fixed mount, toggle control.","salesMarkdown":"The EZC100H3016 is a 3-pole molded-case circuit breaker from the EasyPact EZC100H range, rated 16 A at 40 °C (trip unit TM-D, thermal-magnetic). The 'H' breaking capacity code delivers 100 kA Icu at 110–130 V AC, 50 kA at 220–240 V AC, 30 kA at 380–415 V AC, 20 kA at 440 V AC, and 10 kA at 550 V AC — all per IEC 60947-2. On the DC side it holds 10 kA at 125 V DC (1P) or 250 V DC (2P). No earth-leakage protection built in — if you need GFCI, add an external Vigi module. Fixed backplate mount, front connections both line and load sides. Dimensions: 130 mm high, 75 mm wide, 60 mm deep — fits a standard 3-pole MCCB footprint with 25 mm connection pitch. IP20 finger-safe on the front; IK07 impact resistance means it survives a moderate tool drop during installation. Current-production part — no end-of-life notice. The EasyPact EZC100H series is Schneider's economy molded-case breaker line for distribution duty.","metaTitle":"Schneider Electric EZC100H3016 EasyPact EZC100H Circuit Brea","metaDescription":"Schneider Electric EZC100H3016 EasyPact EZC100H 3-pole circuit breaker, 16 A thermal-magnetic TM-D trip unit, breaking capacity up to 100 kA at 240 V AC. Sourced to order against R","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fb955a0c6af02eee8eb18028ed008480.pdf","sourceUrl":"https://www.se.com/eg/en/product/EZC100H3016/circuit-breakereasypact-ezc100h-tmd-16a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H3016/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H3016","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H3016 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}