{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H3035","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H3035","canonicalUrl":"https://aoctrl.com/schneider/EZC100H3035","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H3035","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, 3-pole, 35 A thermal-magnetic MCCB, TM-D trip unit, 10–100 kA Icu across voltage range, IEC 60947-2.","salesMarkdown":"The Schneider Electric EZC100H3035 is a 3-pole EasyPact EZC100H circuit breaker with a TM-D thermal-magnetic trip unit rated 35 A at 50 °C. The 35 A In is set at 40 °C; the 50 °C derating is already baked into the trip unit marking — no further reduction needed at that temperature. The H breaking capacity code delivers 10 kA Icu at 550 V AC, 30 kA at 400 V AC, 50 kA at 240 V AC, and 100 kA at 110–130 V AC. At 125 V DC single-pole it holds 10 kA; double-pole series connection gives 10 kA at 250 V DC. That spread means it handles high-fault commercial mains without cascading upstream — the 30 kA at 400 V covers typical European industrial supply. The 690 V rated insulation voltage (Ui) and 550 V operational voltage (Ue) AC keep it within standard 400/480 V panel buswork with margin. ## Deployment context This breaker is a fixed-mount, front-connect distribution device sized for backplate mounting in a panel or enclosure. The 75 mm width and 60 mm depth fit standard MCCB footprints on a 25 mm connection pitch. IP20 finger protection means it is safe for open-panel installation inside a locked enclosure; IK07 impact resistance handles accidental tool strikes during maintenance. The toggle control gives positive contact indication, so a quick visual confirms open/closed state without powering a status lamp.","metaTitle":"Schneider Electric EZC100H3035 EasyPact EZC100H 3P 35A Circu","metaDescription":"Schneider Electric EZC100H3035 EasyPact EZC100H 3P 35A thermal-magnetic MCCB. 10-100 kA Icu depending on voltage. TM-D trip unit. IEC 60947-2. Quoted to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Molded Case Circuit Breakers (MCCB)"],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Standards":"EN/IEC 60947-1 JIS C8201-2-2 EN/IEC 60947-2 GB/T 14048.2","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"35 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"3P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"35 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/c4151d08b95991a19a1d45d083657cd0.pdf","sourceUrl":"https://www.se.com/id/en/product/EZC100H3035/ptccbodaphotointegration/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H3035/alternatives.json"},"ai":{"faq":[{"question":"What is the breaking capacity of EZC100H3035 at 400 V AC?","answer":"At 380–400 V AC 50/60 Hz, the EZC100H3035 delivers 30 kA Icu per IEC 60947-2. At 415 V it holds the same 30 kA. At 440 V it drops to 20 kA."},{"question":"Where can I buy EZC100H3035?","answer":"The EZC100H3035 is sourced and quoted to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time."},{"question":"What standards does EZC100H3035 comply with?","answer":"It complies with EN/IEC 60947-1, EN/IEC 60947-2, JIS C8201-2-2, and GB/T 14048.2. It is certified for isolation per IEC 60947-2."},{"question":"What is the difference between EZC100H3035 and a standard EZC100N breaker?","answer":"The H suffix denotes a higher breaking capacity (30 kA at 400 V vs 25 kA for the N code at the same voltage). Both share the same frame, trip unit family, and 35 A TM-D rating — the H version is specified where fault current exceeds 25 kA."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H3035","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H3035 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}