{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H3100","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H3100","canonicalUrl":"https://aoctrl.com/schneider/EZC100H3100","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H3100","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H3100, 3-pole thermal-magnetic circuit breaker, 100 A rated current, 10–100 kA breaking capacity, toggle control, IP20, backplate mount.","salesMarkdown":"The EZC100H3100 is a 3-pole thermal-magnetic circuit breaker from the EasyPact EZC100H family, rated 100 A at 40 °C ambient (100 A at 50 °C with the TM-D trip unit). No earth-leakage protection is built in — if you need that, add a separate RCD or specify the EZC with a Vigi module. Breaking capacity varies by voltage: 100 kA Icu at 240 V AC, 30 kA at 400 V AC, 10 kA at 550 V AC, and 10 kA at 250 V DC (2-pole series). The 'H' in EZC100H means the high-breaking version — it clears faults up to 100 kA at the lower voltages, which covers most distribution panels fed from a transformer. For DC circuits, the 10 kA at 125 V DC (1-pole) or 250 V DC (2-pole) is adequate for industrial control power supplies. Mounting is fixed to a backplate — no DIN-rail adapter in this variant. The front connection (both line and load) keeps wiring accessible when the breaker is panel-mounted. IP20 finger-safe terminals; Also carries GB/T 14048.2 (China) and JIS C8201-2-2 (Japan) — so it's accepted in panels destined for Asia-Pacific markets. The toggle handle gives positive contact indication (you see the position). Mechanical durability is 13,000 cycles — that's the number of on-off operations before wear-out. For a distribution breaker that cycles a few times a year, that's decades of service. Electrical endurance depends on the load current and voltage; for motor-starting duty, derate the cycle count.","metaTitle":"Schneider EZC100H3100 EasyPact EZC100H Circuit Breaker, 100","metaDescription":"Schneider Electric EZC100H3100 EasyPact EZC100H thermal-magnetic circuit breaker, 100 A rated current, 3 poles, 10–100 kA breaking capacity, IEC 60947-2. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"75 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60664-1 3 conforming to IEC 947-1","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 400...415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":"$58.77","priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/a1d40febf1a79697c3a4619f0d7fcd02.pdf","sourceUrl":"https://www.se.com/vn/en/product/EZC100H3100/circuit-breakereasypact-ezc100h-tmd-100a-3-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H3100/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H3100","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H3100 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}