{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H4015","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H4015","canonicalUrl":"https://aoctrl.com/schneider/EZC100H4015","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H4015","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, 4-pole MCCB, 15 A thermal-magnetic TM-D trip, 30 kA Icu at 400 V AC, fixed mount, front connection, IP20.","salesMarkdown":"The front-front connection (line and load both from the front) keeps wiring straightforward in a standard backplate layout. ## Breaking capacity — what those numbers mean The Icu (ultimate breaking capacity) varies by voltage, and the right column for your panel voltage is what governs the installation. At 380…400 V AC the breaker interrupts 30 kA; at 220…240 V AC it handles 50 kA. On DC circuits it's rated 10 kA at 125 V DC (single-pole) or 250 V DC (two-pole in series). If your system's prospective short-circuit current exceeds these numbers, you need a larger-frame breaker upstream. Mounts fixed to a backplate — no DIN-rail clip, so plan for screw-down or bolted mounting. Dimensions are 100 mm wide, 130 mm high, 60 mm deep, with a 25 mm connection pitch between poles. The IP20 finger-safe enclosure is fine for a closed panel; IK07 impact rating means it survives the odd dropped tool during commissioning. If your environment is cleaner (PD2), you still meet the requirement easily. Designed and tested to JIS C8201-2-2, EN/IEC 60947-1, EN/IEC 60947-2, and GB/T 14048.2. It carries a 'suitability for isolation' marking per IEC 60947-2, so you can use it as a visible-break disconnect — the positive contact indication (toggle position shows contact state) confirms the circuit is open. No integral earth-leakage protection; if you need that, add an external RCD or specify the EZC100H with a Vigi module.","metaTitle":"Schneider Electric EZC100H4015 EasyPact EZC100H 15A 4P MCCB,","metaDescription":"Schneider Electric EZC100H4015 EasyPact EZC100H 15A 4-pole MCCB. Thermal-magnetic TM-D trip, 30 kA Icu at 400 V AC. Distribution duty, front connection, IP20. Quoted to order.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Obsolete","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"100 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/d67fea063c14d978f73adc69fefa043b.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H4015/circuit-breaker-easypact-ezc100h-tmd-15-a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H4015/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H4015","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H4015 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}