{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H4030","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H4030","canonicalUrl":"https://aoctrl.com/schneider/EZC100H4030","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H4030","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H, EZC100H4030, 4P thermal-magnetic MCCB, 30 A at 40 °C, 10-100 kA Icu, IP20, toggle control, backplate mount.","salesMarkdown":"The breaking capacity is where this part earns its keep: 100 kA Icu at 110-130 V AC, 50 kA at 220-240 V AC, 30 kA at 380-400 V AC, and 20 kA at 440 V AC — all per IEC 60947-2. That's a lot of fault-current headroom for a 30 A frame, so it handles high-available-fault panels without cascading upstream. On the DC side it manages 10 kA Icu at 125 V DC (1P) and 250 V DC (2P). It complies with EN/IEC 60947-2, EN/IEC 60947-1, GB/T 14048.2, and JIS C8201-2-2. The IP20 finger-safe enclosure and IK07 impact resistance mean it's suited for panel-mount where incidental contact and light mechanical knock are expected. Backplate-mounted with a fixed connection pitch of 25 mm. The toggle actuator gives positive contact indication, so you can see the state at a glance without relying on aux contacts. Dimensions are 130 mm high, 100 mm wide, 60 mm deep — a compact footprint for a 4-pole 30 A MCCB with this interrupting rating. ## Environmental limits and durability Mechanical durability is 13,000 cycles — that's the expected life under no-load switching; the electrical life will be lower under load and depends on the fault and switching frequency. The 690 V AC rated insulation voltage gives margin above the 550 V AC operational maximum.","metaTitle":"Schneider Electric EZC100H4030 EasyPact EZC100H, 30 A, 10-10","metaDescription":"Schneider Electric EZC100H4030 EasyPact EZC100H MCCB, 30 A thermal-magnetic, 10-100 kA Icu, IP20, EN/IEC 60947-2. Sourced to order against an RFQ.","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"100 mm","title":"EZC100H4030","Height":"130 mm","Standards":"EN/IEC 60947-2 EN/IEC 60947-1 GB/T 14048.2 JIS C8201-2-2","description":"circuit breaker, EasyPact EZC100H, TMD, 30A, 4 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Short-circuit protection Overload protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"30 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"30 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/8c589f5feef528e442b730b91ecf5504.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H4030/circuit-breaker-easypact-ezc100h-tmd-30a-4-poles-3d/"},"ai":{"faq":[{"question":"What are the key ratings of the EZC100H4030?","answer":"The EZC100H4030 is a 30 A thermal-magnetic MCCB with a breaking capacity of 100 kA Icu at 110-130 V AC, 50 kA at 220-240 V AC, 30 kA at 380-400 V AC, 20 kA at 440 V AC, and 10 kA at 550 V AC — all per IEC 60947-2. On DC it delivers 10 kA Icu at 125 V DC (1P) and 250 V DC (2P)."},{"question":"Where can I buy the EZC100H4030?","answer":"The EZC100H4030 is sourced to order against an RFQ through independent distribution. Availability and current pricing are confirmed at quote time — no stock count or lead-time number is published here because the supply picture shifts daily."},{"question":"What standards does the EZC100H4030 comply with?","answer":"It complies with EN/IEC 60947-2, EN/IEC 60947-1, GB/T 14048.2, and JIS C8201-2-2. It is suitable for isolation per IEC 60947-2 and carries an IP20 finger-safe enclosure with IK07 impact resistance."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H4030","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H4030 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}