{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H4032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H4032","canonicalUrl":"https://aoctrl.com/schneider/EZC100H4032","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H4032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H4032, 4-pole molded case circuit breaker, 32 A, thermal-magnetic TM-D trip unit, breaking capacity code H, 10-100 kA Icu.","salesMarkdown":"The Schneider Electric EZC100H4032 is a 4-pole molded case circuit breaker from the EasyPact EZC100H range, rated 32 A at 40 °C with a thermal-magnetic TM-D trip unit. The 'H' breaking capacity code means it delivers 100 kA Icu at 110-130 V AC, 50 kA at 220-240 V AC, 30 kA at 380-400 V AC, and 20 kA at 440 V AC — figures that govern its use in high-fault distribution panels where SCCR coordination is critical. At 125 V DC (1P) and 250 V DC (2P) it still holds 10 kA Icu, so it handles DC bus applications in the same footprint. The 32 A rating at 50 °C on the trip unit means you get the full 32 A continuous without derating up to that ambient — above that, the thermal element starts to shift. Mounting is fixed backplate, not DIN rail — plan for a dedicated cutout or enclosure backplate. Front connections both top and bottom simplify bus-bar routing in a distribution board. The 25 mm connection pitch matches standard MCCB terminal spacing for lug or fork terminals. The EZC100H4032 is certified to EN/IEC 60947-2 (the main MCCB standard for industrial applications), EN/IEC 60947-1 (general rules), plus GB/T 14048.2 (China) and JIS C8201-2-2 (Japan). IP20 finger protection on the front face, IK07 impact resistance per EN 50102. Storage temperature range -35 to 85 °C, operating -25 to 70 °C — wide enough for unheated warehouses or outdoor enclosures in temperate climates.","metaTitle":"Schneider Electric EZC100H4032 EasyPact EZC100H, 32 A, 4P, 1","metaDescription":"Schneider Electric EZC100H4032 EasyPact EZC100H molded case circuit breaker, 32 A, 4 poles, thermal-magnetic TM-D trip unit, breaking capacity up to 100 kA. Sourced to order agains","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":["Circuit Breaker Accessories"],"specifications":{"Depth":"60 mm","Width":"100 mm","title":"EZC100H4032","Height":"130 mm","Standards":"GB/T 14048.2 JIS C8201-2-2 EN/IEC 60947-2 EN/IEC 60947-1","description":"circuit breaker, EasyPact EZC100H, TMD, 32A, 4 poles 3d","Control type":"Toggle","Network type":"DC AC","Mounting mode":"Fixed","Trip unit name":"TM-D","Protection type":"Overload protection Short-circuit protection","lifecycle_stage":"current","Connection pitch":"25 mm","Local signalling":"Positive contact indication","Mounting support":"Backplate","Pollution degree":"3 conforming to IEC 60947","Range of product":"EasyPact","Trip unit rating":"32 A at 50 °C","Breaking capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Device short name":"Easypact EZC100H","Network frequency":"50/60 Hz","Poles description":"4P","Upside connection":"Front","Device application":"Distribution","[In] rated current":"32 A at 40 °C","Downside connection":"Front","Circuit breaker name":"Easypact EZC100H","Trip unit technology":"Thermal-magnetic","Utilisation category":"Category A","Mechanical durability":"13000 cycles","Breaking capacity code":"H","IK degree of protection":"IK07 conforming to EN 50102","IP degree of protection":"IP20 conforming to IEC 60529","Earth-leakage protection":"Without","Product or component type":"Circuit breaker","Suitability for isolation":"Yes conforming to IEC 60947-2","Neutral protection setting":"Without protection","Protected poles description":"3t","[Ui] rated insulation voltage":"690 V AC 50/60 Hz conforming to IEC 60947-2","[Ue] rated operational voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","Ambient air temperature for storage":"-35...85 °C","Ambient air temperature for operation":"-25...70 °C","[Ics] rated service breaking capacity":"5 kA at 125 V DC conforming to IEC 60947-2 5 kA at 250 V DC conforming to IEC 60947-2 5 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2 2.5 kA at 550 V AC 50/60 Hz conforming to IEC 60947-2 15 kA at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 25 kA at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 50 kA at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 7.5 kA at 415 V AC 50/60 Hz conforming to IEC 60947-2","[Uimp] rated impulse withstand voltage":"6 kV conforming to IEC 60947-2"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"stockQuantity":0,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fde08f1618fd46d70ecaff5158a90c6d.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H4032/circuit-breaker-easypact-ezc100h-tmd-32a-4-poles-3d/"},"ai":{"faq":[{"question":"Where can I buy EZC100H4032 and how do I get a price?","answer":"The EZC100H4032 is sourced to order against an RFQ through independent distribution. Submit a request for quote (RFQ) to confirm current availability and pricing — no stock figures or lead-time numbers are published here."},{"question":"What is EZC100H4032's breaking capacity at 400 V AC?","answer":"The EZC100H4032 delivers 30 kA Icu at 380-400 V AC 50/60 Hz conforming to IEC 60947-2, and the same 30 kA at 415 V AC. At 440 V AC it drops to 20 kA Icu."},{"question":"What compliance documentation does the EasyPact EZC100H range provide?","answer":"The EZC100H4032 is certified to EN/IEC 60947-2, EN/IEC 60947-1, GB/T 14048.2, and JIS C8201-2-2. It carries IP20 and IK07 protection ratings and is suitable for isolation per IEC 60947-2."}],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"icboms-matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H4032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H4032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-07-22T19:47:38.189Z","lastPublished":"2026-07-22T19:47:38.189Z","indexable":true}}