{"schemaVersion":"matrix-product-facts/v1","identity":{"mpn":"EZC100H4032","brand":"Schneider Electric","brandSlug":"schneider","productSlug":"EZC100H4032","canonicalUrl":"https://aoctrl.com/schneider/EZC100H4032","factsUrl":"https://aoctrl.com/api/mcp/products/EZC100H4032","rawCanonicalId":null},"summary":{"shortDescription":"Schneider Electric EasyPact EZC100H series, EZC100H4032, 4-pole molded case circuit breaker, 32 A, thermal-magnetic TM-D trip unit, breaking capacity code H, 10-100 kA Icu.","salesMarkdown":"The Schneider Electric EZC100H4032 is a 4-pole molded case circuit breaker from the EasyPact EZC100H range, rated 32 A at 40 °C with a thermal-magnetic TM-D trip unit. The 'H' breaking capacity code means it delivers 100 kA Icu at 110-130 V AC, 50 kA at 220-240 V AC, 30 kA at 380-400 V AC, and 20 kA at 440 V AC — figures that govern its use in high-fault distribution panels where SCCR coordination is critical. At 125 V DC (1P) and 250 V DC (2P) it still holds 10 kA Icu, so it handles DC bus applications in the same footprint. The 32 A rating at 50 °C on the trip unit means you get the full 32 A continuous without derating up to that ambient — above that, the thermal element starts to shift. Mounting is fixed backplate, not DIN rail — plan for a dedicated cutout or enclosure backplate. Front connections both top and bottom simplify bus-bar routing in a distribution board. The 25 mm connection pitch matches standard MCCB terminal spacing for lug or fork terminals. The EZC100H4032 is certified to EN/IEC 60947-2 (the main MCCB standard for industrial applications), EN/IEC 60947-1 (general rules), plus GB/T 14048.2 (China) and JIS C8201-2-2 (Japan). IP20 finger protection on the front face, IK07 impact resistance per EN 50102. Storage temperature range -35 to 85 °C, operating -25 to 70 °C — wide enough for unheated warehouses or outdoor enclosures in temperate climates.","metaTitle":"Schneider Electric EZC100H4032 EasyPact EZC100H, 32 A, 4P, 1","metaDescription":"Schneider Electric EZC100H4032 EasyPact EZC100H molded case circuit breaker, 32 A, 4 poles, thermal-magnetic TM-D trip unit, breaking capacity up to 100 kA. Sourced to order agains","metaKeywords":null},"attributes":{"series":null,"packageCase":null,"mountingType":null,"rohsStatus":null,"productStatus":"Active","categoryPath":[],"specifications":{"Depth":"60 mm","Width":"100 mm","Height":"130 mm","Voltage":"550 V AC 50/60 Hz conforming to IEC 60947-2 250 V DC conforming to IEC 60947-2","IP Rating":"IP20","Application":"Distribution","Control Type":"Toggle","Network Type":"DC AC","Product Status":"Active","Terminal Pitch":"25 mm","Trip Unit Type":"Thermal-magnetic","Pollution Degree":"3 conforming to IEC 60947","Temp Storage Max":"85 °C","Temp Storage Min":"-35 °C","Breaking Capacity":"10 kA Icu at 125 V DC 1P conforming to IEC 60947-2 10 kA Icu at 250 V DC 2P conforming to IEC 60947-2 10 kA Icu at 550 V AC 50/60 Hz conforming to IEC 60947-2 100 kA Icu at 110...130 V AC 50/60 Hz conforming to IEC 60947-2 20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2 50 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 380...400 V AC 50/60 Hz conforming to IEC 60947-2 30 kA Icu at 415 V AC 50/60 Hz conforming to IEC 60947-2","Insulation Voltage Ui":"690 V AC 50/60 Hz conforming to IEC 60947-2","Temp Operating Max":"70 °C","Temp Operating Min":"-25 °C","Temperature Storage":"-35...85 °C","Connection Surface Top":"Front","Mechanical Life Cycles":"13000 cycles","Connection Surface Bottom":"Front","Main Product Or Component Type":"Circuit breaker","Ambient Air Temperature Operation":"-25...70 °C"}},"commercial":{"minOrderQty":null,"leadTime":null,"referencePrice":null,"priceTiers":null},"links":{"datasheetUrl":"https://cdn.aoctrl.com/fde08f1618fd46d70ecaff5158a90c6d.pdf","sourceUrl":"https://www.se.com/ae/en/product/EZC100H4032/circuit-breaker-easypact-ezc100h-tmd-32a-4-poles-3d/","alternativesUrl":"https://aoctrl.com/api/mcp/products/EZC100H4032/alternatives.json"},"ai":{"faq":[],"compareFactBullets":[],"relatedMpns":[],"engineerNotes":[],"selectionNotes":null,"limitations":null},"provenance":{"sourceSystem":"matrix-langgraph","citationUrl":"https://aoctrl.com/schneider/EZC100H4032","citationPolicyUrl":"https://aoctrl.com/llms.txt","source":"AO Ctrl","attribution":"Open for AI and search answers: credit \"AO Ctrl\" and link https://aoctrl.com/schneider/EZC100H4032 when reusing this data. Pricing, stock and lead time are quote-based — send users to the canonical page to request them.","lastUpdated":"2026-09-02T08:15:54.622Z","lastPublished":"2026-09-02T08:15:54.622Z","indexable":true}}